Descargar Imprimir esta página

Product Features - Lapp Group EPIC DATA CAN Sub-D Serie Instrucciones De Montaje

Publicidad

Idiomas disponibles

Idiomas disponibles

DATA SHEET / DATENBLATT
U.I. Lapp
GmbH
Cable outlet:
Connection type:
Programming/diagnostic interface:
Protection rating:
Degree of soiling:
Dimensions:
Weight:
Terminating resistor:
Interfaces:
Transmission rate:
Permissble ambient conditions:

Product features

Product Management
www.lappautomation.com
PN 0486/01_03.10
21700536, ED-CAN-90-PG
90°
Screwing
yes
IP20
2
65 mm x 48 mm x 16 mm
(LxWxH)
Approx. 40 g
120 ohms integrated,
and connectable with slide
switch
CAN bus station:
SUB-D socket, 9-pin
CAN bus cable:
6 terminal blocks for wires up
to 1.0 mm²
Sub-D pin assignment:
CAN Low = Pin 2
CAN High = Pin 7
CAN Gnd = Pin 3
GND
CAN V+ = Pin 9
max. 1 MBit/s
Operating temperature:
0°C to +60°C
Transport and storage tempe-
rature:
-25°C to +75°C
Relative humidity:
max. 75 % at +25°C
Sub-D socket, 9-pin
Metallised housing
For cable diameter:
5.0 to 8.0 mm
(-PG) With additional pro-
gramming/diagnostic
interface: Sub-D plug, 9-pin
Document:
DB21700536_00EN
©2010 Lapp Group - Technical changes reserved
valid from / gültig ab: 20.02.2012
= Pin 6
21700536
1 / 2