Luminous button
CENTRAL
BUTTON
Detector/wiring
fault
1
The input indicator corresponding to the active button will turn on.
6.- Maintenance
Clean the surface of the equipment with a soft cloth, water and soap.
Ÿ
Do not use abrasive detergents, petrol, alcohol or solvents, as this might damage the sensor.
Ÿ
AKO guarantees the calibration of the detectors during the first 3 years from the date of
Ÿ
purchase, and after this time, it is advisable to replace the detector.
We recommend changing the detector in the event of having been exposed to high gas concentrations.
Ÿ
According to standard EN-378, the correct operation of the detector should be checked at
least once a year, ask about if your current local regulations require lower intervals.
CHECK METHOD
Preparation:
Disconnect the unit's power supply, open the detector's cover and turn the delay switch to "Without delay".
Ÿ
Close the cover and connect the unit's power supply again. Wait for 5 minutes before making the check.
Ÿ
Start of the check:
AKO-52211 (Type A): Put a normal lighter 5 cm underneath the detector and release gas for 4 seconds.
Ÿ
AKO-52212 (Type B): Put a normal lighter 10 cm underneath the detector and release gas for 2 seconds.
Ÿ
Check that:
The pre-alarm activates after a few seconds. The detector's green indicator turns off and the red indicator
Ÿ
starts to flash. The station beeps intermittently. The pre-alarm relay activates.
The alarm then activates, and the detector's red indicator turns on permanently. The alarm station emits a
Ÿ
two-tone sound. The alarm relay activates.
The alarms disappear after 1 to 2 minutes. The detector's red indicator turns off and the green indicator
Ÿ
starts to flash slowly. The alarm and pre-alarm relays deactivate.
ALARM STATION
ACOUSTIC
1
2
3
4
ALARM
Off
Off
1
On
Two-tone sound
On
3 short tones every 2
1
On
On
minutes
20
TRAPPED PERSON
ALARM RELAY
Off
5
6
5
6
5
6
7
7
7