ADDRESSING
The address (1-128) is software set and stored
in a non-volatile memory. The detector can be
addressed, in manual or automatic mode from
the Control Panel. For further details see the
Control Panel's programming manual.
MOUNTING
Lean the detector head on the base; while
pressing, turn it clockwise until it enters in the
seat of the base as illustrated in the figure.
CONNECTIONS
The detector head must be used in conjunction
with SD500 or SD500R standard base.
For example of connections, please refer to the
standard base's SD500 - SD500R manual
In order for the device to work properly, it is
recommended to seal the openings in the base
of the detector used for the cables to go through.
The FDOT500 is only to be used with ELKRON
FAP series Control Panels.
TESTING
(trained personnel)
Before testing, notify to competent authority that
the system is temporarily out of service due to
maintenance operations.
The detectors can be tested in the following way:
A - Smoke Functional test
It is a simulation of smoke presence obtained
from the insertion of rigid white wire (ø <1mm)
in the test hole until the alarm occurs.
B - Smoke entry test
Use a manufacturer-approved test equipment.
•
Use an aerosol canister locked into the
proper test dispenser.
•
Follow the test instruction attached to the
canister.
C - Temperature test
It is a simulation of high temperature.
Use a hot air flow on the thermal element of
detector until the alarm occurs.
At the end of testing operations, restore the
system to normal operation and notify the status
to the competent Authorities.
TECHNICAL SPECIFICATIONS
Light source
Operating voltage
Average power
consumption
(Normal condition)
Average power
consumption
(Alarm condition)
Static Alarm Threshold 58°C +/- 5%
Bi-colour LED
Operating temperature
Relative humidity
Storage/shipping
temperature
Dimensions:
Diameter
Weight
Enclosure material
In compliance with EN54-5: 2000 /A1: 2002
EN54-7: 2000 /A2: 2006
EN54-17: 2005/AC: 2007
Optical Smoke & Heat detector mod. FDOT500
Urmet S.p.A. 1293-CPD-0341
DoP n. 1293-CPR-0341
Further information are available to the manufacturer.
4/8
GaAlAs infrared emitting
diode
20 Vdc (-15%, +10%)
modulated
250 μA @ 20Vdc
2 mA @ 20Vdc
Red steady:
alarm condition
Red blinking slow (2s):
alarm condition with SLC
operating voltage < 17V
Green blinking slow (2s) :
normal condition
Green blinking fast :
duplicate address
-10 ÷ 55°C ± 2°C
(14 ÷ 131°F)
93 % ± 2 %
non-condensing
-30 ÷ 70 °C
(-22 ÷ 158°F)
90 mm (3.54 inc)
Height
40 mm (1.57 inc)
70 g
ABS V0
CLASS A1
08
1293