All wiring must comply with local and national electrical standards and codes and be installed by qua-
lified and skilled electricians.
7.
An individual branch circuit and single receptacle used only for this air conditioner must be available.
See the following table for suggested wire sizes and fuse specifications:
Model
Power supply
<
5.2 kW
220-240V~50Hz
5.2 kW
NOTE!
The supply voltage should be consistent with the rated voltage
of the air conditioner.

Connect the cable to the indoor unit

1.
Indoor/Outdoor connection cable should be H07RN-F type.
2.
Remove the panel and Screw, then remove the window cover.
3.
Connect cables according to their marks to terminals.
4.
Wrap those cables not connected with terminals with insulation tapes, so that they will not touch any
electrical components.
5.
Fit the power cord clamp.
Panel
Window cover
ATTENTION
Always make sure that the electrical connection cables from indoor to outdoor unit are correct
fitted, e.g. when a green electrical line is fitted to clamp with code "L" in the indoor unit the
other end of that same green electrical line should be connected to clamp with code "L" on the
outdoor unit.

Connect the cable to the outdoor unit

See fig. 21
1.
Remove the electric parts cover from the outdoor unit.
2.
Connect the connective cables to the terminals as identified with their respective matched numbers on
the terminal block of indoor and outdoor units.
3.
To prevent the ingress of water, form a loop of the connective cable as illustrated in the installation dia-
gram of indoor and outdoor units.
4.
Insulate unused cords (conductors) with PVC-tape. Make sure they do not touch any electrical or metal
parts.
Input Rated Current
Power Cord Size
(Switch/Fuse)
25A
25A
Terminal block of indoor unit
L
N
S
Cord clamp
To outdoor unit
2.6 kW or 5.2 kW model
1.5mm
2
2.5mm
2
L
N
S
To outdoor unit
3.5 kW
4
61