Ferroli SUN G 20/2 PRO Manual De Instrucciones página 35

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

CHOKE ELECTRODES
1
After removing the cover, detach the high-tension cables
from the transformer side, remove the photo resistance
1, unscrew the connector 2 that hooks the fuel line to the
choke 3, loosen the screws 4 and, turning the flange anti-
clockwise, remove the flange-choke-deflectorelectrode
assembly.
The choke may be cleaned adequately by removing the
4
filter and cleaning inside the spray nozzle and jet with ga-
soline and a light oil rinse. Re-assemble all parts carefully
with special attention to the positioning of the electro-
2
3 4
desdeflector.
ELECTRODES - DEFLECTOR SETTING
After having installed the nozzle, check the correct position of the electrodes and deflector
according to the following levels. It is adviseable to check levels after every intervention on
head.
4÷5
3÷3,5
3,5÷4,5
FAN
WARNING:In the event of replacement or assembly/disas-
sembly of the fan, make sure that the latter does not touch
the motor platform as illustrated in the inclosed diagram.
UK
35

Publicidad

Tabla de contenido
loading

Tabla de contenido