5.8. Plant configuration ()
(password) 1
(Plant type)
0= 2 Pipes (unique changeover coil)
1= 2 Pipes + Heater (cooling coil + electrical post heater)
2*= 4 Pipes (cooling coil + heating coil)
3= 4 Pipes + Heater (cooling coil + heating coil + electrical post heater)
0= Not used
1= Not used
2= Not used
(Post heating valve enable AO3)
(Inverter fan enable)
(Air flow control) reboot the controller after setting
0*=Temperature
1=CO2 (2000ppm)
2=Supply and exhaust pressure, 2 Probes (500Pa)
3=Supply air pressure (500Pa)
4= PIR (occupant sensor) + Temperature
(Humidity)
0*= OFF
1= Dehumidification by digital input
2= Dehumidification by analog input
3= Humidification by digital input
4= Humidification by anlog input
5= Dehumidification /summer) - humidification (wintyer) by analogl input
(Mixing damper enable)
0*= OFF
1= ON (with mixing dampers only)
2= CO2 digital sensor + ON-OFF dampers (DO1)
3= CO2 analog sensor + modulating dampers (AO3)
4= Not used
(Regulation probe)
0 = AI1 (supply air)
1* = Display (SKW keyboard) or return air
(Room regulation probe)
0= Display (SKW keyboard AIR1)
1= Display clamps (SKW keyboard AIR2)
2*= AI5 (return air probe)
(Remote summer / winter changeover enable)
0*= Fresh air sensor
1= Exhaust air sensor
2= Digital input DI3
(Fire alarm managment)
0*= Off, in case of fire alarm the unit is completely stopped
1= On, in case of fire alarm the dampers are open and the fans run at max speed.
2= Available only with Fanl= yes: in case of fire alarm the dampers are open and only the return fans runs at max speed.
(Water coil antifreeze sensor enable)
(Modbus protocol address)
(Modbus protocol
0-1-2= not used
3*= 9600 baud
4= 19200 baud
(Modbus protocol parity
1*= EVEN
2= NONE
3= ODD
(Alarm history reset)
(Password)
* Default value