The multi-mount kit allows any of the 6500 range of beam detectors to be mounted to
either a wall or the ceiling. It is designed to create an additional alignment range in
cases where the detector and reflector cannot be mounted within 10° alignment of each
other. The kit includes the hardware necessary to mount either a single transmitter/
receiver unit or a single reflector. (To mount the transmitter/receiver, the surface mount
kit 6500-SMK is also required). If both the transmitter/receiver and the reflector require
additional alignment range, two kits will be needed. The kit is not compatible with the
long-range reflector kit.
The kit comes partly pre-assembled into the following components (the parts can be
identified by matching the reference numbers to the numbers in Figs 1-3):
Qty.
Description
1
Wall/ceiling fixed bracket
1
T-Bracket
2
M6 x 15mm hex allen head bolts
2
M6 split lock washers
3
M4 x 16mm pan head screws
3
M4 hex nuts
6
M4 washers
3
M4 split lock washers
MOUNTING THE BRACKETS
When installing to a wall or ceiling, use an appropriate anchor method to ensure the
total weight of the assembly can be securely supported. Install the fixed bracket to a
wall or ceiling so that when mounted, the transmitter/receiver and the reflector will have
a clear line of sight between them. Mount the bracket only on solid structures of the
building. To avoid unwanted alarms due to wall movement, do not mount to flexible walls,
such as sheet metal walls (see the Detector Mounting section of the beam detector
manual for more details).
Attach the T-Bracket to the fixed bracket using the allen head bolts as shown in Fig. 1 -
don't forget to use the split lock washers too. Do not fully tighten the bolts until
installation and testing are complete.
MOUNTING AND WIRING INSTRUCTIONS: TRANSMITTER/RECEIVER
The surface mount kit 6500-SMK must be used with the transmitter/receiver to provide
wiring entry.
1. Read the installation instructions of the beam detector to determine the appropriate
number of wires to be used.
2. Drill the appropriate holes for the conduit using the drill centres provided on all four
sides of the surface mount box (see Fig. SMK1-A). Conduit sizes of up to 20mm are
acceptable.
3. Mount the surface mount box on to the T-bracket of the multi-mount kit using the pre-
threaded holes (see Fig. SMK1-B and Fig. 2) and the M4 screws and washers.
For proper operation of the beam detector, the surface mount box must be:
a)
Securely mounted to ensure no subsequent movement of the beam detector will
occur after the installation is completed.
b)
Mounted to ensure there is line of sight between the transmitter/receiver unit
and the reflector. See the beam detector manual for further details.
4. Attach the transmitter/receiver unit (with cover and faceplate removed) securely to
the surface mount box using the four supplied screws.
5. Pull wiring and conduit through the drilled hole(s). Secure conduit fitting as required
(not supplied). Be sure to leave enough wire to reach the connectors.
6. Complete the installation and testing of the transmitter/receiver unit using the
instructions included with the beam detector. Only when installation is complete,
fully tighten the bolts connecting the T-bracket to the fixed bracket. NOTE: Ensure
all bolts are fully tightened to maintain mounting integrity!
MOUNTING INSTRUCTIONS: REFLECTOR
1. Mount the reflector on to the T-bracket of the multi-mount kit using the three M4
screws (see Fig. 3).
For proper operation of the beam detector, the reflector must be:
a)
Securely mounted to ensure no subsequent movement of the reflector will
occur after the installation is completed.
b)
Mounted to ensure there is line of sight between the transmitter/receiver unit
and the reflector. See the beam detector manual for further details.
c)
Mounted so that the reflector is perpendicular to the line of sight of the
transmitter/receiver unit.
2. Complete the installation and testing of the beam detector as per its manual. Only
when installation is complete, fully tighten the bolts connecting the T-bracket to the
fixed bracket (see Fig. 3).
WARNING: If not installed correctly, the BEAM detector may not function properly.
* The 6500-MMK is also compatible with the following models:
BEAM200, BEAM200S, BEAM1224, BEAM1224s,
FSB-200S, FSB-200, BEAM355, BEAM355S
DB200-02-00
Ref. Num
1
2
3
4
5
6
7
8
Important!
Important!
Fig. 1
2
Fig. 2
Fig. 3
5
Fig. SMK1
B
Pittway Tecnologica S.r.l., Via Caboto 19/3, 34147 Trieste, ITALY
3
4
7
7
8
A
B
B
© System Sensor 2007 I56-2625-005
1
5
8
6
7

Publicidad

loading

Resumen de contenidos para System Sensor 6500 Serie

  • Página 1 WARNING: If not installed correctly, the BEAM detector may not function properly. * The 6500-MMK is also compatible with the following models: BEAM200, BEAM200S, BEAM1224, BEAM1224s, FSB-200S, FSB-200, BEAM355, BEAM355S DB200-02-00 © System Sensor 2007 I56-2625-005 Pittway Tecnologica S.r.l., Via Caboto 19/3, 34147 Trieste, ITALY...
  • Página 2 2. Completare l’installazione e la verifica del rilevatore a fascio come riportato nel manuale. Solo al termine dell’installazione serrare a fondo i bulloni che collegano la staffa a T alla staffa fissa (ved. Fig. 3). DB200-02-00 © System Sensor 2007 I56-2625-005 Pittway Tecnologica S.r.l., Via Caboto 19/3, 34147 Trieste, ITALY...
  • Página 3 AVISO: Si el detector por rayo no está bien instalado, es probable que no funcione correctamente. *El 6500-MMK también es compatible con los siguientes modelos: BEAM200, BEAM200S, BEAM1224, BEAM1124S, FSB-200, FSB-200S, BEAM355, BEAM355S. DB200-02-00 © System Sensor 2007 I56-2625-005 Pittway Tecnologica S.r.l., Via Caboto 19/3, 34147 Trieste, ITALY...
  • Página 4 2. Beenden Sie die Installation und testen Sie den Linearen Rauchmelder wie in der zugehörigen Anleitung beschrieben. Nach Abschluss aller Arbeiten ziehen Sie die Haltebolzen zwischen dem T-Stück und dem Montageblech fest an (siehe Abb. 3). DB200-02-00 © System Sensor 2007 I56-2625-005 Pittway Tecnologica S.r.l., Via Caboto 19/3, 34147 Trieste, ITALY...

Este manual también es adecuado para:

6500-mk6500-smk