A - Technical details of the product
Composition:
b housing with body and door made from protected
sheet steel.
Surface coating:
b body/door painted with polyester powder coating. All
shades are RAL, AFNOR compliant.
Degree of protection:
b IP 6X as per the EN 60079-7 and 60079-31
standards.
b the housing offers a degree of protection of IP 66
as per EN 60529.
Operating temperature:
b polyurethane seal on the door ........ - 20 °C + 40 °C
b PA6 closure systems ...................... - 20 °C + 40 °C
b SANTOPRENE hinge plugs............ - 20 °C + 40 °C
The housings are delivered based on the
following configuration:
b body and door pre-assembled.
b 1 M8 inset ground pin allowing for external connection.
b 4 M6 inset pins on the base making it possible to
use external brackets.
NHA1154201-01
B - ATEX Identification
Housings designed for the installation of certified
electrical equipment.
A partial certificate has been issued for the empty
housings of the S3D SPACIAL RANGE.
Type NSYS3DEX... no. LCIE 02 ATEX 0037 U
Our empty housings bear the following identifica-
tion markings :
Type NSYS3DEX housings... are designed to be
used in the fields subject to explosion of zones 1,2
and 21,22.
Type NSYS3DEX housings ... have been examined
as components .
They may only be installed and used following a
new presentation to a notified body (example :
LCIE).
The partial examination certificate for these
housings serves as the basis for a EU standard
examination certificate.