DIMENSIONES CONTROL AQ NX
11.13[282.7]
Optional
Solenoid
10.50 [266.6]
5.25 [133.4]
1.41 [35.8]
(6X) 1/8" NPT PORT 60 APART
ø
*
0.733 [18.62 mm]
4 places
ø
*
0.88
[22.4 mm]
2.45 [62.2]
2.75 [69.9] 2.75 [69.9]
2.06 [52.3]
48ES STAGER
6.42 [163.1]
1.25 [31.7]
11.13[282.7]
.32 [8.1]
1/8" NPT Filtered Inlet
(8X) 1/8" NPT - 45 APART
ø
*
0.733 [18.62 mm]
4 places
ø
*
0.88
[22.4 mm]
*
NOTA:Haga los agujeros según se
requiera. Estos agujeros
serán hechos en la fábrica si
se solicita.
Figura 1
2 • AQ NX Stager Controller MY20
8.91[226.3]
1/8" NPT Drain
3.50 [88.9]
2.72 [69]
2.00 [50.8]
1/8" NPT Filtered Inlet
4.00 [101.6]
6.00 [152.4]
(4X) .19 [4.8]
(4X) R.16 [4]
1/8" NPT Drain
1.75 [44.4]
1/8" NPT Drain
51ES STAGER
ESPECIFICACIONES TECNICAS
SISTEMA SERIE AQ NX48 y AQ NX51
Guía para Medidor de Flujo Genérico
• Salida de señal abierta
• El rango de pulso generado no debe exceder 100 pulsos
por segundo (100 Hz), o 6,000 pulsos por minuto
• Ofrece mediciones del medidor en el rango de 1-255
3
galones (25.5 m
) por cada 1-255 pulsos.
Ejemplo: 35 galones/100 pulsos
(=3.5 galones/10 pulsos, = 0.35 galones/1 pulso)
• El medidor debe operar a 5 VDC
Características Eléctricas
• Alimentación 115 VAC ±20%, 24 VAC salida w/40 VA
(mantener voltaje de entrada en este rango)
• Alimentación 230 VAC ±20%, 24 VAC salida w/40 VA
(mantener voltaje de entrada en este rango)
• Max Potencia Nominal 15W
Humedad
• 95% RH, sin condensación
Temperatura
• Temperatura máxima del flujo de operación 140°F
(60°C)
• Operar donde temperatura ambiente es arriba 0º C
(32°F) y abajo 43º C (110°F)
Presión
• Presión máxima del flujo de operación 125 psi (8.5 bar)
• El flujo de control puede ser agua o aire y debe ser igual
o mayor (10%) que la presión del sistema.