1) Introduction
The BExBG05D is a flameproof beacon which is certified to
meet the requirements of the ATEX directive 94/9/EC and the
IECEx scheme. The beacon produces synchronised visual
warning signals and can be used in hazardous areas where
potentially flammable gas and dust atmospheres may be
present. The BExBG05D has a flash energy level of 5 joules
and can be used in Zone 1 and Zone 2 areas with gases in
groups IIA, IIB and IIC and Temperature Classifications of T1,
T2, T3 and T4. The unit can also be used in a temperature
classification T5, if the upper ambient temperature is
restricted to +55ºC and T6 if the upper ambient temperature
is restricted to +40ºC. The unit can be used in Zone 21 and
Zone 22 areas for combustible dusts and has an IP rating of
IP 67 and a surface temperature rating of T115ºC or T100ºC
if the upper ambient temperature is restricted to +55ºC and
T85ºC if the upper ambient temperature is restricted to
+40ºC.
2) Marking
All units have a rating label, which carries the following
important information:-
BExBG05D
Unit Type No.
Input Voltage: DC Units
12V or 24V or 48V
AC Units
230V or 115V
Codes:
Ex d IIC T4 for Ta –50ºC to +70ºC
Ex d IIC T5 for Ta –50ºC to +55ºC
Ex d IIC T6 for Ta –50ºC to +40ºC
Ex tD A21 IP67 T115ºC based on max. Ta of +70ºC
KEMA 00ATEX2006
Certificate No's
IECEx KEM 10.0002
Epsilon x
Equipment Group and
Category:
CE Marking
Notified Body No.
"Warnings"
DO NOT OPEN WHEN AN EXPLOSIVE
GAS OR DUST ATMOSPHERE IS PRESENT
COVER BOLTS CLASS A4-80
USE HEAT RESISTING CABLES AND CABLE GLANDS
(Rated 110ºC) AT AMB. TEMPERATURES OVER 40ºC
Year of Construction /
Serial No.
i.e. 10 / 1DB13000001
3)
Type Approval Standards
The beacon has EC Type Examination and IECEx certificates
issued by KEMA and have been approved to the following
standards:-
www.acornfiresecurity.com
INSTRUCTION MANUAL (ATEX / IECEx)
BExBG05D Flameproof Xenon Beacons
For use in Flammable Gas and Dust Atmospheres
II 2G/D
0518
www.acornfiresecurity.com
EN60079-0:2006 IEC60079-0:2004 (Ed4)
EN60079-1:2007 IEC60079-1:2007 (Ed6)
EN61241-0:2006 IEC61241-0:2004 (Ed1)
EN61241-1:2004 IEC60079-1:2004 (Ed1)
4)
Installation Requirements
The beacons must be installed in accordance with the latest
issues of the relevant parts of the EN60079 standards or the
equivalent IEC standards – Selection, Installation and
maintenance of electrical apparatus for use in potentially
explosive atmospheres (other than mining applications or
explosive processing and manufacture):-
EN60079-14:2008
Electrical Installations in Hazardous
IEC60079-14:2007 (Ed4)
Areas (other than mines)
EN60079-10:2003
Classification of Hazardous Areas
IEC60079-10:2008 (Ed1)
The installation of the units must also be in accordance with
any local codes that may apply and should only be carried
out by a competent electrical engineer who has the
necessary training.
5)
Zones, Gas Group, Category, IP Rating and
Temperature Classification
The BExBG05D beacons have been certified Ex d IIC T4 for
Ta –50ºC to +70ºC, Ex d IIC T5 for Ta –50ºC to +55ºC and
Ex d IIC T6 for Ta –50ºC to +40ºC for gas and IP67 T115ºC
based on max. Ta of +70ºC.
be installed in locations with the following conditions:-
Area Classification Gas:
Zone 1
Explosive gas air mixture likely to occur in
normal operation.
Zone 2
Explosive gas air mixture not likely to occur,
and if it does, it will only exist for a short time.
Gas Groupings:
Group IIA
Propane
Group IIB
Ethylene
Group IIC
Hydrogen and Acetylene
Temperature Classification:
T1
400
T2
300
T3
200
T4
135
T5
100
T6
85
General Requirements
Flameproof Enclosure 'd'
Dust General
Requirements
Dust Enclosures tD
This means that the units can
o
C
o
C
o
C
o
C
o
C
Amb. +55ºC
o
C
Amb. +40ºC