Logo! Am2 Aq - Festo LOGO! 8 TP EduTrainer Instrucciones De Servicio

Ocultar thumbs Ver también para LOGO! 8 TP EduTrainer:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

7.4 LOGO! AM2 AQ

Technical data LOGO! AM2 AQ expansion module
Supply power
Input voltage
Permissible range
Current consumption
Power failure buffering
Power loss at 24 V DC
Electrical insulation
Reverse polarity protection
Analog outputs
Number
Voltage range
Load voltage
Current output
Load current
Resolution
Cycle time analog output (depending on the installation)
Electrical isolation
Cable length, (shielded and twisted)
Error limit voltage output
Short circuit protection output voltage
Overload protection current output
Output voltage
Please refer to expansion modules for the LOGO! 8 manual for further information.
© Festo Didactic 8086581
24 V DC
20.4 V DC to 28.8 V DC
30 mA to 82 mA
Approx. 10 ms
0.7 W to 2.0 W
No
Yes
2
0 V DC to 10 V DC
≥5 kΩ
0/4 mA to 20 mA
≤250 Ω
10 bits normalized to 0 to 1000
50 ms
No
Max. 10 m
±2,5 % full scale
Yes
Yes
Yes
®
LOGO! 8 TP EduTrainer
– Operating instructions
31

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

8084384

Tabla de contenido