04: ECO habilitado / desactivado
Interfaz
05: AECO habilitado / desactivado
Interfaz
06:
ECO voltage range setting
Interfaz
Configuración
Parameter 2: Enable or disable ECO function. You may choose
the following two options:
ENA: Modo ECO activado
DIS: Modo ECO desactivado
Configuración
ENA: Modo ECO Avanzado activado
DIS: Modo ECO Avanzado desactivado
Configuración
Parameter 1 & 2: Set the acceptable high voltage point and
low voltage point for ECO & AECO mode by pressing Down key
or Up key.
HS: High loss voltage in ECO & AECO mode in parameter 2.
For 200/208/220/230/240 VAC models, the setting range in
parameter 3 is from +7V to +24V of the nominal voltage.
(Default: +12V)
For 100/110/115/120/127 VAC models, the setting range in
parameter 3 is from +3V to +12V of the nominal voltage.
(Default: +6V)
LS: Low loss voltage in ECO & AECO mode in parameter 2.
For 200/208/220/230/240 VAC models, the setting range in
parameter 3 is from -7V to -24V of the nominal voltage.
(Default: -12V)
For 100/110/115/120/127 VAC models, the setting voltage in
parameter 3 is from -3V to -12V of the nominal voltage.
(Default: -6V)
15
(Default)
(Default)