2.1 Assembly Site Requirements
The REFUSOL
vertical wall. The device is attached by means of a self-centering wall-mounting plate.
•
The assembly site must be shaded.
•
The device may only be mounted in a vertical position.
•
This requires a firm wall or metal structure. Do not attach the device to wooden
boards, wallboards or the like! Please note that the device weighs 40 kg / 88.18492
lbs. The load-carrying capacity of the wall and the attachment of the device(s) must be
designed based on this weight (pertinent construction rules must be observed)!
•
Mount the device at an appropriate distance from combustible materials.
•
We recommend that you mount the device at eye level to ensure optimum user comfort.
•
Owing to its protection type (IP66), the device can also be mounted in outside areas.
•
To allow for the heat dissipation required, keep the following minimum distances from
the ceiling and wall as well as from neighbouring devices.
Minimum
distances
CAUTION
22
®
is provided with convection cooling and is therefore designed for attachment to a
Note:
To prevent accidents when installing and servicing, free and safe ac-
cess to the devices must be ensured.
Note:
Do not cover the cooling ribs of the heat sink. Failure to observe this
specification could void your warranty.
At the sides
150 mm or
5.9055 inches
®
REFU SOL
should in never be mounted on top of each other, otherwise
the convection cooling will be affected!
At the
400 mm or
top
15.748 inches
Copyright REFU Elektronik GmbH
At the
500 mm or
bottom
19.685 inches