F6-BOOST TROUBLESHOOTING
Problem
Unit will not turn ON
Recovery process is slow
Unit does not pull
a vacuum
RED LED Code
Optional Tank Overfill
2 Flashes
Sensor has been activated
High Pressure Swich as
3 Flashes
been activated
4 Flashes
Motor Fault
JB INDUSTRIES • F6-BOOST Operating Manual • 630.851.9444 • sales@jbind.com
10
Possible Cause
Unit not properly plugged in or
no power at power source
Defective Power Switch or PCB
Plugged INLET Filter
Valve core on system being
recovered not fully depressed
Compressor seals are worn
Loose hose connections on
IN Side
Compressor seals are worn
Fault Indicated
Check power cord to ensure properly
plugged into power source and IEC
inlet
Replace defective electrical component
Check INLET port filter, Clean or replace
Check core depressor on connecting
hoses
Rebuild compressor, replace piston seal
Tighten hose connections
Replace piston seals
Possible Solution
Tank overfill sensor has activated.
Replace recovery tank.
Tank overfill sensor cord not connected. Either connect to a
recovery tank equipped with overfill sensor, or install a shorting
plug on the end of the Tank Overfill Sensor cord.
Pressure on the discharge of the unit exceeded 550 PSIG. Check
to make sure all valves in the discharge pathway are open. Once
corrected, the pressure switch will reset. If equipped with manual
high pressure switch, push reset button.
Excessive pressure in recovery tank. Replace recovery tank.
Let cool down for 5-10 minutes and restart.
Compressor Mechanism is jammed. Repair will be required to
fix the compressor mechanism.
Solution