Wiring the Control Panel
1
Locate conduit entrance at the bottom of the enclosure as
shown. Check local codes for the number of power circuits
required. The schematic is located on the inside cover of the
control panel.
CAUTION!
Be sure the incoming voltage is the same as the pump motor
nameplate.
Providing separate pump and control/alarm power sources is
recommended.
Type 4X conduit must be used to maintain a Type 4X rating
of the control panel.

Setup and Operation

Rotate dial and press to select the corresponding pump's mode indicator or panel settings icon.
Duplex Model Shown
CAUTION!
Seal the electrical conduit with an approved
sealing compound to prevent moisture or
gases from entering into the control panel.
E4
HAND
OFF
PUMP 1
1
AUTO
HAND
PUMP 2
OFF
2
(duplex only)
AUTO
HOA
2
Connect the following wires to the proper terminals:
incoming power for each pump circuit breaker
incoming power for control/alarm
pump 1
pump 2 (duplex only)
C-Level™ sensor
oat switches (recommended)
See schematic label on inside cover of the control panel for
details.
3
Verify correct operation of control panel after installation is
complete.
SETTINGS
Counts and ETMs
- Displays pump run time and counts of pump run and alarms
Timer Settings
- Con gures timers (Timed Dose mode only)
Level Settings
- Con gures level setpoints
Alternation (duplex only) - Con gures alternation mode for duplex panels
Advanced
- Con gure advanced functions and view troubleshooting tools
1
Alarm System (Indicator Light and Horn)
When an alarm condition occurs, the red light and
horn will be activated.
1
If the TEST/SILENCE button is pressed and released,
the horn will be silenced. When the alarm condition
is cleared, the alarm system is reset.
2

Circuit Breakers

Each pump circuit has a thermal-magnetic circuit
breaker that provides branch circuit protection and a
means to disconnect the pump.
3
Float Test Switches
Push to simulate a oat closure condition for each
input.
4
Dry Auxiliary Contacts
2
Normally Open - Contacts are OPEN under normal
conditions and CLOSED when alarm condition is
present. CLOSED during power loss.
3
Automatically resets once alarm condition is cleared.
Aux contact rating: 120V, 5A
4
NOTE
If redundant o
installed in its place.
oat is not used, a jumper must be
PN 1067499A 11/21
© 2021 SJE, Inc. All Rights Reserved.