TX207
①
134.9
[5.31]
4.8
[0.19]
33.8
[1.33]
mm [Inch]
②
③
④
Wiring diagrams
187 [7.36]
Supply voltage
147
[5.79]
X2 – RS422/RS485 (COM2) + CAN (CAN0)
X3 – RS422/RS485 (COM3) + CAN (CAN1)
174.9 [6.89]
X4 – RS232 (COM1) + RS232 (COM4)
Technical Data/Certification Data
Device
Type
ID
Power Supply
Supply voltage
Current consumption
System resources
Display, colors, resolution
Brightness
Touchscreen
CPU
Operating system
Flash/RAM
Real Time Clock, RTC Back-up
Buzzer
Interface
Ethernet ports
USB ports
General information
Operating temperature
Storage temperature
Relative humidity
Protection class
Weight
EMV
UL
1
1 = 24 VDC
2
2 = 0 V
3 =
3
1 = CAN - GND
2 = CAN - terminating resistor
3 = CAN - CAN-H
4 = CAN - CAN-L
7 1
5 = CAN - terminating resistor
6 = RS485 - terminating resistor
7 = RS485 - GND
8 = RS485 - terminating resistor
9 = RS485 - Y (TX+)
10 = RS485 - Z (TX-)
11 = RS485 - A (RX+)
12 = RS485 - B (RX-)
1 = GND (COM1)
2 = TX
(COM1)
3 = RX
(COM1)
6 1
4 = RTS (COM1)
5 = CTS (COM1)
6 = GND (COM4)
7 = TX
(COM4)
8 = RX
(COM4)
9 = RTS (COM4)
10 = CTS (COM4)
TX207-P3CV01
100002080
24 V DC (10 to 32 VDC)
0.3 A at 24 VDC (max.)
7" TFT 16:9, 64K, 800 × 480, WVGA
Typ. 200 Cd/m², dimming up to 0 %
Resistive
32 bit RISC dual core, 800 MHz
Linux RT
4 GB/1 GB
Yes
No
2, 10/100 Mbps
1 (Host V 2.0, max. 100 mA)
0...50 °C (vertical installation)
-20...+70 °C
5...85 % RH, non condensing
IP66 (front), IP20 (rear), Type: 2, 4X
0.560 kg
For installation in industrial environments:
– emission EN 61000-6-4,
– immunity EN 61000-6-2
cULus (UL File No. E484727)
ANSI/UL 508
CAN/CSA C22.2 No. 142
© Hans Turck GmbH & Co. KG | 100002509 2022-08