Notes on mounting and wiring Auxiliary Switches for UL/CSA labeled models:
– M22-K(10)(01) have screw terminals. M22-CK(10)(01)(20)(02)(11) have clamp terminals.
– Switch modules are snapped into place at the locations shown in the diagrams that follow.
– Switches will function as either "standard" or "trip/alarm" contacts depending on their mounting location.
– Location "HIN" refers to standard operation. Location "HIA" refers to "trip/alarm" operation.
– Follow the numbering and wiring scheme provided above depending on the contact location and function. (N.O. or N.C.)
– Permissible contact configuration: 1 HIA and/or 2 HIN.
Note:
After mounting of the M22... switch is complete, check off the appropriate box on the auxiliary switch
label provided on the side of the breaker or switch.
1
1
OFF
2
PZ2
3
3
2
M22-K10, M22-K01
4a
(Screw Terminals)
→PN1
HIA
HIN
a = 6 - 10 mm
(a = 0.24 - 0.4"
2
1 x 0.75 - 2.5 mm
2 x AWG18 - AWG14
UL/CSA = Cu only
PZ 2
0.8 Nm (7 lb-in)
-NA
I
= I
th
e
-CNA
(UL/CSA)
U
(V)
I
(A)
e
e
600 AC
5 A
250 DC
1 A
Pilot Duty Ratings:
B 600, Q 300
Above 300 V AC
Same polarity
3
1
2
4/6