Briteq power distributor PD-32A Manual De Instrucciones página 4

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

ENGLISH
FUNCTIONS
(PD-32A)
1. RESIDUAL CURRENT CIRCUIT BREAKER: this is a vital security device of the power distributor!
When someone accidentally touches one of the mains conductors, a current leak through the body of
this person could result in a lethal (deadly) shock. As soon as such current leakage in the installation is
detected, the power distributor outputs will be disconnected. The maximum allowable current leakage is
set to 30mA. Under normal working conditions the lever on the right should be in upward position.
Important: the functions of this device should be tested every 30days by pushing the test button on top:
as a result the outputs should be immediately disconnected from the mains.
2. INDIVIDUAL CIRCUIT BREAKERS: each of the 3 phases is secured by two C16 automatic circuit
breakers. Under normal working conditions the lever should be in upward position.
3. VOLT METERS: each of the 3 phases have their individual 3-digit voltage meter.
4. AMPERE METERS: each of the 3 phases have their individual 3-digit ampere meter.
5. 32A INPUT: 1,5m long mains input cable (3x 32A, 5wire), equipped with CEE (3P+N+E) inlet plug.
6. 32A OUTPUT: CEE (3P+N+E) outlet socket (3x 32A, 5wire), can be used to feed-through up to 32A
3phase current. Make sure that the total input current will not be exceeded!
7. 16A OUTPUT PHASE1: two 230V/16A output sockets, connected to phase1 (L1)
8. 16A OUTPUT PHASE2: two 230V/16A output sockets, connected to phase2 (L2)
9. 16A OUTPUT PHASE3: two 230V/16A output sockets, connected to phase3 (L3)
BRITEQ
®
OPERATION MANUAL
3/30
PD-32A / PD-63A
ENGLISH
FUNCTIONS
(PD-63A)
1. RESIDUAL CURRENT CIRCUIT BREAKER: this is a vital security device of the power distributor!
When someone accidentally touches one of the mains conductors, a current leak through the body of
this person could result in a lethal (deadly) shock. As soon as such current leakage in the installation is
detected, the power distributor outputs will be disconnected. The maximum allowable current leakage is
set to 30mA. Under normal working conditions the lever on the right should be in upward position.
Important: the functions of this device should be tested every 30days by pushing the test button on top:
as a result the outputs should be immediately disconnected from the mains.
2. INDIVIDUAL CIRCUIT BREAKERS: each of the 4 outputs (A, B, C, D) is secured by three C32
automatic circuit breakers. Under normal working conditions the lever should point to the right.
3. VOLT METERS: each of the 3 phases have their individual 3-digit voltage meter.
4. AMPERE METERS: each of the 3 phases have their individual 3-digit ampere meter.
5. 63A INPUT: 1,5m long mains input cable (3x 63A, 5wire), equipped with CEE (3P+N+E) inlet plug.
6. 32A 3PHASE OUTPUT A: CEE (3P+N+E) outlet socket (3x 32A, 5wire. This output is secured by the 3
C32 automatic circuit breakers marked "A" on the front panel.
7. 32A 3PHASE OUTPUT B: CEE (3P+N+E) outlet socket (3x 32A, 5wire. This output is secured by the 3
C32 automatic circuit breakers marked "B" on the front panel.
8. 32A 3PHASE OUTPUT C: CEE (3P+N+E) outlet socket (3x 32A, 5wire. This output is secured by the 3
C32 automatic circuit breakers marked "C" on the front panel.
9. 32A 3PHASE OUTPUT D: CEE (3P+N+E) outlet socket (3x 32A, 5wire. This output is secured by the 3
C32 automatic circuit breakers marked "D" on the front panel.
BRITEQ
®
OPERATION MANUAL
4/30
PD-32A / PD-63A

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Power distributor pd-63a

Tabla de contenido