Descargar Imprimir esta página

Sime AQUA 25 ErP LN Instrucciones Para El Instalador página 87

Ocultar thumbs Ver también para AQUA 25 ErP LN:

Publicidad

Idiomas disponibles

Idiomas disponibles

4.9.1 Diagnostics of the cause of fault
Diagnostics of the
cause of fault
Error code table of multicolor signal lamp (LED)
Red blink code of signal
lamp
2 blinks
3 blinks
4 blinks
5 blinks
6 blinks
7 blinks
8 blinks
9 blinks
10 blinks
During the time the cause of fault is diagnosed, the control outputs are dead
The burner remains shut down
-
Fault status signal (alarm) at terminal 10, according to the error code table
-
The diagnostics of the cause of fault is quit and the burner switched on again by
resetting the burner control. Press the lockout reset button for about 1 second (<3
seconds).
Alarm at
Possible cause
term. 10
On
No establishment of flame at the end of safety
time (TSA)
- Faulty or soiled fuel valves
- Faulty or soiled flame detector
- Poor adjustment of burner, no fuel
- Faulty ignition equipment
On
Free
On
Extraneous light on burner startup
On
Free
On
Free
On
Too many losses of flame during operation
(limitation of the number of repetitions)
- Faulty or soiled fuel valves
- Faulty or soiled flame detector
- Poor adjustment of burner
On
Time supervision oil preheater
On
Free
Off
Wiring fault or internal fault, fault output
contacts, faults that cannot be detected, such as
simultaneous faults, other faults
87

Publicidad

loading