PLEASE READ AND FOLLOW THESE INSTRUCTIONS!
This sheet contains important safety instructions that must be followed during the installation and operation of the device. Follow all warnings
on the unit and in this sheet.
HAzARDOUS LOCATIONS SAFETY PRECAUTIONS
!
The device has been investigated for Class I, Division 2 Groups A, B, C, D/Class I, Zone 2, Groups IIC Hazardous Locations and should meet the following
conditions for safe use when installed in these hazardous locations:
• The equipment shall only be used in an area of not more than pollution degree 2, as defined in IEC/EN 60664-1.
• The equipment shall only be used in an enclosure that provides a degree of protection not less than IP54 in accordance with IEC/EN 60079-0.
• The operating temperature class (T-code) of this device is T4.
!
WARNING – Explosion Hazard:
• Do not connect or disconnect when energized.
• No user serviceable parts. Do not open the unit. Do not substitute components inside.
• Hazardous Locations Marking:
• IEC 60079-0:2017 / EN IEC 60079-0:2018 and IEC 60079-7:2015+A1:2017 / EN IEC 60079-7:2015+A1:2018
•
U L 121201, CSA 213 - Class1, Div 2, Groups ABCD T4 UL 60079-0, UL 60079-7 - Class I, Zone 2 AEx ec IIC T4 Gc
CSA C22.2 No. 60079-0, CSA C22.2 No. 60079-7 - Class 1, Zone 2 Ex ec IIC T4 Gc U
E137632
E234790
TECHNICAL SPECIFICATIONS
SCM-E-EIP - Input: 11.3 - 16.6 V, 300 mA
gENERAL INSTALLATION SAFETY PRECAUTIONS
!
• Install the unit in a temperature and humidity-controlled environment.
• Do not place the unit close to heat-emitting sources. To allow proper ventilation do not block or cover the top and bottom sides of the unit.
• Ensure the module is properly installed on a DIN rail.
Model
Input Cable
SCM-E-EIP
Molex 367690901 (provided with module)
SCM-W-HRT7
Molex 367690901 (provided with module)
OPERATINg SAFETY PRECAUTIONS
!
!
CAUTION - Burn Hazard: Do not touch the chassis unless the device is disconnected from power and has cooled down.
• Do not remove the cover, as this device has no user-serviceable parts inside.
• To turn OFF the device, disconnect the input cable from the SDN-D power supply.
gENERAL OPERATINg INFORmATION
Operating Ambient Temperature Range: -40ºC to 70ºC
TECHNICAL SUPPORT
1-800-377-4384 • 1-847-268-6651 • solahd.technicalservices@emerson.com • https://www.appleton.emerson.com/en-us/shop/appleton/solahd-sdn-d
SolaHD, 9377 W. Higgins Road, Rosemont, IL 60018 USA
USER MANUAL - For detailed information, download the complete User Manual with the QR code or contact Technical Support for a paper copy.
While every precaution has been taken to ensure accuracy and completeness in this manual, Appleton Grp LLC d/b/a Appleton Group assumes no responsibility, and disclaims all liability for damages resulting from use of this
information or for any errors or omissions. Specifications are subject to change without notice.
P/N: A272-371 Rev. 1 12/2021
© 2021 Appleton Grp LLC d/b/a
Appleton Group. All rights reserved.
SAFETY INSTRUCTION SHEET
SCM Communications Modules
For use with SolaHD
II 3 G Ex ec IIC Gc, INERIS 21ATEX3004U,
SCM-W-HRT7 - Input: 11.6 - 16.8 V, 65mA
Output Cable
Cat6 Ethernet Cable or higher
Min #24 AWG twisted Pair wire for run less than 5000ft and #20 AWG for longer distances
SDN-D Power Supplies
TM
IECEx
Ex ec IIC Gc, IECEx INE 21.0061U