TN-S Network System, 2+0
F1
L
L
N
N
PE
PE
F2
*
MET
*
TN-C Network System, 3+0
F1
L1
L1
L2
L2
L3
L3
PEN
PEN
F2
*
MET
*
LEGEND:
* If connection  > 0.5 m make connection .
Mode of protection
1+0
L-N, L-PEN, L-PE, N-PE (only TN-S)
3+0
L-PEN
2+0
L-PE, N-PE
4+0
L-PE, N-PE
Not green / Nicht grün Autre que vert /
Green / Grün
Vert / Verde
No es verde / Non verde
1.42 [36]
.71
[18]
max. 2.7 [70]
max. 2.7 [70]
max. 2.7 [70]
inches
[mm]
TN-S Network System, 4+0
F1
L1
L1
L2
L2
L3
L3
N
N
PE
PE
F2
*
MET
*
SPD Conductor min. cross section
z PE / PEN
SPD Earthing Conductor
ø min 6 mm
2
L / N
SPD Live Conductor
ø min 2.5 mm
2
Replace Plug
Sustituya la conexión
Stecker ersetzen
Remplacez la prise
Sostituire la cartuccia
2.84 [72]
2.13 [54]
max. 2.7 [70]
PH2 / SLOT ¼
4.5Nm
[39.9 lbf∙in]
Product name:
SG2... 1P, 2P, 3P, 4P...A300(R)
U
/U
AC (50-60Hz)
240 V + 6%
o
n
U
/ MCOV
AC
300V
C
U
1500 V
p
VPR (per UL 1449)
900 V
I
(8/20)
20 kA
n
I
(8/20) (per UL 1449)
20 kA
n
I
(8/20)
50 kA
max
I
/ Backup fuse
50 kA / 250A gG fuse
SCCR
(per IEC 61643-11)
25 kA / 315A gG fuse
SCCR (per UL 1449)
150 kA
I
≤ 0.400 mA
PE
Ta
-40 ºC to +85 ºC [-40 ºF to +185 ºF]
RH
5 %...95 %
Mounting
35mm DIN rail, EN 60715
Altitude (max)
4000 m [13123 ft]
Location / Number of ports / IP
Indoor / 1 / 20 (built-in)
Minimum distance from any confuctive surface
0 mm
Terminals:
ø min 1.5 mm
(solid, stranded) 18 mm
ø min 1.5 mm
(flexible) 18 mm
ø min 0.25 mm
RC push in (solid)
10 mm
ON
OFF
OFF
Green / Grün
Vert / Verde
Unplugged / Nicht eingesteckt
Débranché / Desconectado
Scollegato
(1+0)
(2+0), (3+0), (4+0)
Green / Grün
Vert / Verde
Unplugged / Nicht eingesteckt
Débranché / Desconectado
Scollegato
ON
OFF
ON
A.C.
D.C.
RC contact(s) states / Fernmeldekontakt(e)-Status
SPD module(s) functional / installation is protected
250V / 1A
48V / 0.5A
SPD-Modul(e) funktional / Installation ist geschützt
125V / 1A
24V / 0.5A
SPD module(s) unplugged or non-functional /
installation is unprotected | SPD-Modul(e) nicht eingesteckt oder
12V / 0.5A
nicht funktional /Installation ist ungeschützt
Protection against short circuit
L
I
= 50kA
SCCR
S1
F1
F1 ≤ 250A gG
F1 > 250A gG
F2
F2 not needed
F2 ≤ 250A gG
Conductor dimensioning
F1
≤ 40A
63A —80A
100A — 125A
160A — 200A
F2
-
-
-
-
S2
S1
6mm
2
10mm
2
25mm
2
25mm
S2
6mm
2
10mm
2
25mm
2
25mm
2
/ ø max 35 mm
2
[ø min 15 AWG / ø max 2 AWG]
2
/ ø max 35 mm
2
[ø min 15 AWG / ø max 2 AWG]
2
/ ø max 1.5 mm
2
[ø min 23 AWG / ø max 16 AWG]
Step 1: Unlock / Schritt 1: Entsperren /
ON
OFF
ON
Étape 1: Déverrouillage / Paso 1: Desbloquear /
Fase 1: Sbloccare
Not green / Nicht grün
Autre que vert / No es
verde / Non verde
Not green / Nicht grün
Green / Grün
Green / Grün
Autre que vert / No es
Vert / Verde
Vert / Verde
verde / Non verde
Step 2: Pull module out / Schritt 2: Modul herausziehen /
Étape 2: Extrayez le module / Paso 2: Sacar el módulo /
ON
OFF
OFF
Fase 2: Tirare fuori la cartuccia
11- 12
11-14
Closed
Open
Geschlossen
Offen
Open
Closed
Offen
Geschlossen
NOTE: If the I
is
I
= 25kA
SCCR
SCCR
declared higher than 50 kA
up to 100 kA use 160 A
F1 ≤ 315A gG
F1 > 315A gG
gG fuse.
F2 not needed
F2 ≤ 315A gG
>250A
>315A
≤ 250A
≤ 315A
2
25mm
2
25 / 35mm
2
2
25mm
2
25 / 35mm
2