IntesisBox
LG-RC-MBS-1
6. Códigos de Error
Error en el
Error en
Control
Modbus
Remoto
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
32
33
34
35
36
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
57
59
60
© Intesis Software S.L. – Todos los derechos reservados
Información sujeta a cambios sin previo aviso
®
IntesisBox
es una marca registrada de Intesis Software SL
1
Room air sensor fault
2
Indoor unit pipe in sensor fault
3
communication fault between wired remote controller and indoor unit
4
Drain pump fault
5
Communication fault between indoor unit and outdoor unit
6
Indoor unit pipe out sensor fault
7
Indoor unit mode runs on opposite to outdoor unit
8
N/A
9
EEPROM memory fault
10
BLDC motor signal fault or motor lock
11
HEX middle point sensor fault
12
heater terminal block sensor fault
13
N/A
14
N/A
15
N/A
16
N/A
17
Outlet air sensor fault
18
Return air sensor fault
19
No communication response from sub PCB to main PCB
20
No communication response from main PCB to sub PCB
21
IPM fault
22
AC input is over current (RMS)
23
DC link low or high voltage
24
High pressure or low pressure switch on
25
High/low input voltage
26
Compressor start failure
27
PSC/PFC fault
28
DC link high voltage
29
Over current at compressor input
32
Discharge temperature is high at inverter compressor
33
Discharge temperature is high at constant speed compressor
34
High pressure is too high
35
Low pressure is too low
36
Compression ratio is too low
39
Communication fault between PFC and inverter PCB
40
CT sensor fault
41
Discharge sensor at inverter compressor is fault
42
Low pressure sensor is fault
43
High pressure sensor is fault
44
Air sensor at outdoor unit is fault
45
HEX sensor at outdoor unit is fault
46
Compressor suction sensor is fault
47
Discharge sensor at constant speed compressor is fault
48
HEX outlet sensor at outdoor unit is fault
49
IPM temperature sensor is fault
50
Missing phase among 3 phase
51
Over combination ratio
52
No communication from inverter PCB detected at main PCB
53
Communication fault between indoor and outdoor unit
54
Reverse phase is detected
57
No communication from main PCB detected at inverter PCB
59
Wrong outdoor unit combination
60
Inverter EEPROM memory fault
Manual de Usuario r1.1 esp
Descripción del Error
URL
http://www.intesis.com
Email
info@intesis.com
tel
+34 938047134
16 / 17