Supply air temperature measurement is done with NTC sensor included with the unit.
Activate the thermostat with On/Off selector (FIG.2B)
Define supply air temperature desired adjusting the frontal wheel (FIG.2C)
Select operation mode (heating or cooling) with selector located in frontal cover (FIG.2A)
NOTICE: Before selecting cooling operation mode in WCT thermostat, be sure that the unit
incorporate a specific cold water coil with corresponding condensation plate and drain system.
Do not use this WCT thermostat in cold operation mode in combination with internal coils of
CADB-HE DC, CADB-N DC heat recovery units or COR-NW air curtains.
5. Settings
In order to adapt thermostat response for different installations needs, it is possible to change
proportional range.
The WCT is supplied as default with a range proportional value of 3°C. If three-way valve control is
shown unstable, it is possible to change the range to 5°C changing the jumper position located in
the internal board (FIG 3-A).
6. Technical features
Mechanical characteristics
Casing material
Dimensions
Connections
Mounting
Protection degree
Isolation
Electrical characteristics
Voltage
Electrical consumption
Input/Output characteristics
Analog inputs (temperature sensors)
Operation conditions
Temperature setpoint
Maximum ambient temperature
Maximum relative humidity
Vibration
8
Self-extinguishing plastic ABS V0 white colour
110x74x26 mm
Cable terminals of 1,5 mm
On wall
IP20
Class II
VAC 50Hz
Max. 6 VA
NTC sensor (R
=10K). Long cable=4m.
25
15°C to 30°C
50°C
95%
0°C to 50°C
2