Inputs – Menu (2 of 6) | AI1, AI2, DI1 and DI2
Main Menu
Sub Menu
= scroll menu items
M ain M enu
= scroll menu items
PrSs
(Pressure)
C onf ig Input
AI1
AI2
DI1
APPS
(Applications)
DI2
InPt
(Inputs)
OutP
(Outputs)
tMp
(Temperature)
Mot
(Motor)
Setc
(Settings)
rMp
(Ramps)
NET
(Network)
HrS
(Time & Date)
btN
(Buttons)
https://www.innes.com.mx/
*** To save any changes, press
on INTRM24VAV***
*** To the previous step without saving, press
on INTRM24VAV***
= select / set value
AI1
AI1 Signal Type
MSV.1
OFF
(disabled)
Go to "AI2"
EtS
(external temp sensor)
SENs
C H O ver Set pnt
(sensor)
NoCl
24°C
(normally cool)
AV.58
NoHt
(normally heat)
Go to "AI2"
StFl
(setpnt airflow 0-10Vdc)
CO2
C O 2 M axim um Range
(carbon dioxide)
ASt
2000 ppm
AV.140
(Air supply temp sensor)
mor
(Motor position)
E50
Go to "AI2"
(external 50k sensor)
tES
E (Tstat temp. sensor)
StPt
(Tstat setpoint 0-10Vdc)
StPt
(Tstat setpoint 2-10Vdc)
= select / set value
AI2
AI2 S ignal T ype
MSV.2
OFF
Go to "DI1"
(disabled)
EtS
(external temp sensor)
SENs
C H O ver Set pnt
(sensor)
NoCl
24°C
(normally cool)
AV.58
NoHt
Go to "DI1"
(normally heat)
StFl
(setpnt airflow 0-10Vdc)
CO2
C O 2 M axim um Range
(carbon dioxide)
ASt
2000 ppm
(Air supply temp sensor)
AV.140
mor
(Motor position)
E50
(external 50k sensor)
Go to "DI1"
tES
E (Tstat temp. sensor)
StPt
(Tstat setpoint 0-10Vdc)
StPt
(Tstat setpoint 2-10Vdc)
= select / set value
DI1
NS B-O C C C ont act
MSV.10
OFF
Go to "DI2"
OCCo
(occupancy open)
O C C M inim um Tim e in M in
OCCc
(occupancy closed)
30 min
(0-240)
AV.62
nSbo
(night set back open)
NS B O ver ide del ay M in
nSbc
(night set back closed)
120 min
(0-180)
AV.60
unod
(unoccupied damper)
Go to "DI2"
NS B Heat ing set pnt
= select / set value
DI2
16°C / 61°F
DI2 S ignal T ype
MSV.14
AV.19
Go to "OutP"
OFF
Ovrd
(override all)
DI2 C ont act
BV.36
OVH1
NO
(override heat 1)
(normally open)
OVH2
(override heat 2)
NC
(normally closed)
OVHt
(override all heat)
NoCl
(normally cool)
NoHt
(normally heat)
Go to "OutP"
unod
(unoccupied damper)
Configuration
Go to "AI2"
C O 2 S et pnt
Go to "AI2"
800 ppm
AV.141
To display CO
without generating
2
an alarm, use a setpoint higher than
2000ppm or the CO
Maximum
2
Range (highest of the 2).
Go to "DI1"
C O 2 S et pnt
Go to "DI1"
800 ppm
AV.141
To display CO
without generating
2
an alarm, use a setpoint higher than
2000ppm or the CO
Maximum
2
Range (highest of the 2).
No O C C O ver ide Del ay M in
No O C C H eat ing set pnt
120 min
16°C / 61°F
(0-180)
AV.61
NS B M ode
BV.20
StP
(setpoint)
Off
NS B C ool ing set pnt
NS B M ot or M ode
MSV.36
Auto
28°C / 82°F
AV.18
OPEn
DI2 D el ay S econds
Go to "OutP"
120
(0-3600)
AV.64
INCTR14VAV Standard
Controlador de VAV
Manual de especificación e Instalación
No O C C C ool ing set pnt
Go to "DI2"
28°C / 82°F
AV.19
AV.18
Go to
"OutP"
Page | 8