Descargar Imprimir esta página
OJ Electronics MTC-1991-UFH Guía Instalación Rápida
OJ Electronics MTC-1991-UFH Guía Instalación Rápida

OJ Electronics MTC-1991-UFH Guía Instalación Rápida

Publicidad

Enlaces rápidos

INSTRUCTIONS
Type MTC with air sensor or floor sensor
57915B 11/18 (SJR)
English
MTC is an electronic heating thermostat
designed to be installed in a standard single
gang electrical box with a minimum width of
2-1⁄4". Once installed, it requires no
maintenance.
An LED illuminates to indicate „call" for heating,
this also aids in system testing. An ON/OFF
selector switch on the front of the cover makes
system operation extremely simple.
PRODUCT LINE
With 16A relay switch, °F-scale
240V supply
MTC-1991-UFH
with floor sensor
MTC-1999-UFH
with built-in air sensor
120V supply
MTC-2991-UFH
with floor sensor
MTC-2999-UFH
with built-in air sensor
24V
MTC-3991-UFH
with floor sensor
MTC-3999-UFH
with built-in air sensor
With 16A relay switch , °C-scale
240V supply
MTC-1991-UCH
with floor sensor
MTC-1999-UCH
with built-in air sensor
120V supply
MTC-2991-UCH
with floor sensor
MTC-2999-UCH
with built-in air sensor
24V supply
MTC-3991-UCH
with floor sensor
MTC-3999-UCH
with built-in air sensor
CLASSIFICATION
The product is class II device (240V, 120V) and
a class III device (24V) according to UL 8730-1.
WARNING
The system may not be energized unless
the system is installed according to this
instruction and the installation meets all
applicable codes.
Warranty is void if not installated according to
this instruction and proper procedure.
TECHNICAL DATA
Power supply (model dependent) .... 24, 120 and
240V AC ±10%, 50-60 Hz
Output relay, SPST (resistive load) ................16A
Built-in switch ....................................2 pole, 16A
Ambient operating
temperature ............................32-122°F (0-50°C)
Scale limitation ............. minimum and maximum
Scale range ..........................50-122°F (10-50°C)
Temperature setback ......................not available
On/Off differential ............................0.7°F (0.4°C)
Enclosure ......................................................IP20
Dimensions (H
x
x
4.5"x3.3"x2.0"
W
D) .................
(115x84x50 mm)
Environment and recycling
Please help us to protect the environment by
disposing of the packaging in accordance with
the national regulations for waste processing.
Recycling of obsolete appliances
Appliances with this label must not
be disposed off with the general
waste. They must be collected
separately and disposed off
according to local regulations.
FLOOR SENSOR INSTALLATION
(where applicable)
The sensor shall be mounted in a conduit
which should be sealed and placed as high as
possible in the concrete, etc. The sensor wiring
may be extended up to 150' (50 m) using 18
gauge wire and the wiring resistance shall not
exceed 20 ohms. Sensor wires must be kept in
a separate conduit, away from all other wiring.
The sensor and wires must be protected from
damage during the installation. If shielded wire
is used, it must not be grounded but connected
to terminal 6 on the thermostat.
ERROR DETECTION
The MTC has built-in error detection which will
de-energize the heating circuit if the sensor is
damaged or if it detects an open or shorted
sensor circuit.
CAUTION!
Disconnect all electrical power prior to
installing or servicing this unit.
THERMOSTAT INSTALLATION (fig. 1-2)
1. Remove thermostat knob, noting the
position (A).
2. Loosen screw to remove frame and cover
(B).
3. Attach wiring from the rear of the thermostat
according to the wiring diagram.
4. The thermostat is mounted in a standard
single gang electrical box with a minimum
width of 2-1/4". Please ensure that the
adapter plate is properly clipped on the
thermostat.
- re-install frame and cover
- re-install the knob in the proper position
TEMPERATURE SETTING/ADJUSTMENT
Adjust the temperature knob to the desired
room or floor temperature, if after a few
days you find the temperature to be different
from the setting, adjustment can be made
as follows: Measure the room temperature
with thermometer, remove the knob without
rotating it, then reposition the knob according
to the measured temperature on the scale and
re-install it.
MAXIMUM/MINIMUM TEMPERATURE
LIMITATIONS
Behind the knob there are red and blue locking
rings held in position by a screw. To set the
limitations, loosen the screw (C) and adjust the
red limit ring to the desired maximum, set the
blue ring to the desired minimum temperature,
then retighten the screw. The knob must be
re-installed exactly as it was removed.
© 2018 OJ Electronics A/S
Français
Type MTC avec capteur thermique ou
capteur de sol.
MTC est un thermostat électronique pour
installation de chauffage dont la conception
permet une installation directe dans un boîtier
électrique encastré standard avec un largeur de
min. 2-1⁄4" et ne demande aucun entretien une
fois installé.
Une diode électroluminescente "LED" s'allume
pour faire "appel" à la source de l'installation
de chauffage, celle-ci sert aussi en cas d'un
contrôle éventuel du système (test). Un
commutateur "Marche/Arrêt" placé sur la partie
frontale du couvercle permet une exploitation
du système d'une extrême simplicité.
LIGNE DE PRODUIT
Avec contact de relais de 16 A, pour °F
Alimentation 240V
MTC-1991-UFH
avec capteur de sol
MTC-1999-UFH
avec capteur incorporé
Alimentation 120V
MTC-2991-UFH
avec capteur de sol
MTC-2999-UFH
avec capteur incorporé
Alimentation 24V
MTC-3991-UFH
avec capteur de sol
MTC-3999-UFH
avec capteur incorporé
Avec contact de relais de 16 A, pour °C
Alimentation 240V
MTC-1991-UCH
avec capteur de sol
MTC-1999-UCH
avec capteur incorporé
Alimentation 120V
MTC-2991-UCH
avec capteur de sol
MTC-2999-UCH
avec capteur incorporé
Alimentation 24V
MTC-3991-UCH
avec capteur de sol
MTC-3999-UCH
avec capteur incorporé
CLASSIFICATION
Ce produit est un appareil de classe II (240V,
120V) et de classe III (24V) selon UL8730-1.
DANGER
Le système ne devra jamais être mis sous-
tension avant que celui-ci soit installé en
fonction des instructions d'installation et
que toutes les conditions nécessaires soient
comblées.
La garantie ne sera plus valable si les
instructions et procédures d'installation ne sont
pas respectées.
FICHE TECHNIQUE
Tension d'alimentation (selon le modèle) ....... 24,
120 & 240V CA ±10%, 50-60 Hz
Relais sortie, SPST (charge résistive) ...........16 A
Commutateur incorporé .............. bipolaire, 16 A
Température ambiante
d'exploitation ...................... 32°-122°F (0°-50°C)
Limites de l'échelle ........... minimum & maximum
Étendue de l'échelle ......... 50°-122°F (10°-50°C)
Température programmable........ non-disponible
Différentiel Marche/Arrêt ................0,7°F (0,4°C)
Protection ....................................................IP 20
Dimensions (H x l x P) .................4,5"x3,3"x2,0"
(115x84x50 mm)

Publicidad

loading

Resumen de contenidos para OJ Electronics MTC-1991-UFH

  • Página 1 Étendue de l’échelle ..50°-122°F (10°-50°C) disposing of the packaging in accordance with Température programmable..non-disponible Différentiel Marche/Arrêt ....0,7°F (0,4°C) the national regulations for waste processing. Protection ............IP 20 Dimensions (H x l x P) ....4,5”x3,3”x2,0” (115x84x50 mm) © 2018 OJ Electronics A/S...
  • Página 2 à la valeur maximum désirée, puis favorable al medio ambiente. amenez la bague bleue à la valeur minimum désirée et ensuite revissez (C). Le bouton devra être remis avec précision à sa place. © 2018 OJ Electronics A/S...
  • Página 3 Fig. 1 Fig. 2 - with floor sensor / avec capteur du sol Fig. 2 - with built-in sensor / avec capteur incorporé PE: Ground, use as required PE: Ground, use as required ˚F © 2018 OJ Electronics A/S...
  • Página 4 The trademark is registered and belongs to OJ Electronics A/S · © 2018 OJ Electronics A/S...

Este manual también es adecuado para:

Mtc-1999-ufhMtc-2991-ufhMtc-2999-ufhMtc-3991-ufhMtc-3999-ufhMtc-1991-uch ... Mostrar todo