Descargar Imprimir esta página

Elektrotechnik Schabus GX-B1 Instrucciones De Uso página 9

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 27
Placing of the unit for city and
natural gas (methane CH4):
Plug the unit into a socket at a height of 15-30 cm
below the ceiling but no further than 4 m from the
gas appliance.
Note that the alarm unit must be mounted above the
highest door or window opening in the room.
City and natural gas (methane) are lighter than air
and will therefore always rise.
Placing of the alarm unit for liquefied gas
(propane C3H8 / butane C4H10):
Plug the unit into a socket at a height of 15-30 cm
above the floor but no further than 4 m from the gas
appliance. Escaping liquefied gas is heavier than air
and sinks to the floor. It spreads across the floor rat-
her like water - but as a gas - and always seeks the
lowest point.
The alarm unit may not be used in the following positions:
places where the sensor is shielded from escaping gas (e.g. behind curtains or in
cupboards)
directly above hearths or points of combustion or over a wash basin or sink
next to a door, windows, ventilator, fan, air conditioning unit etc.
in areas where dust or dirt can prevent the sensor from working
in areas at risk of explosion.
START-UP
The GAS ALARM GX-B1 is simply plugged into a 230V/50Hz socket. The LED indicator
(function) will light up yellow. The sensor of the monitoring system requires a warm-up time
of 3-5 minutes to become fully operational. The LED indicator (function) will then light green
and the GAS ALARM GX-B1 is operational.
NOTE: various transport conditions (lengthy storage / humidity) can lead to an alarm state
being triggered immediately after the warm-up time (LED flashes red). Disconnect the unit
briefly from the supply and start the warm-up process again. You may need to repeat this
procedure up to three times.
GAS ALARM
GAS ALARM

Publicidad

loading

Este manual también es adecuado para:

300224