UNIT DESCRIPTION
The PW Passive Infrared Wall Switch sensors use advanced
passive infrared (PIR) technology.
• The PW sensor has Optional Neutral capability for
applications requiring neutral wiring. It also has Multi-Way
available on all models.
• A "walk-through" mode can turn lights off after only 3
minutes, if no activity is detected after 30 seconds following
an occupancy detection.
• The PW-311 has one relay with dimming control capability
and two buttons to allow control of the dimming.
• PW sensors contain a light level sensor. If adequate daylight
is present, the sensor holds the load OFF until light levels
drop, even if the area is occupied. See the Light Level
Adjustment section.
BUTTON FUNCTIONS
Pressing and holding the UP button will ramp the lights up to
the maximum value as determined by the High Trim setting.
Pressing and holding the DOWN button will dim the lights down
to the minimum value as determined by the Low Trim setting. See
Additional Programming Features for detail on setting the trim.
Tapping the UP button when the load is OFF sets the load to the
last non-zero value.
Tapping the UP button when the load is ON sets the load to the
maximum (high trim) value.
Tapping the UP button twice when the load is OFF turns the load
to its maximum (high trim) value.
Tapping the DOWN button when the load is ON, turns the load OFF.
INSTALLATION
TURN OFF THE POWER AT THE CIRCUIT
BREAKER BEFORE INSTALLING THE SENSOR.
1. Make sure that the power has been turned OFF at the circuit
breaker.
2. Connect wires to the PW flying leads as shown in the wiring
diagram that is appropriate to the PW model and electrical
supply. The ground wire (green) must be fastened to ground
for the sensor to work properly.
3. Attach the sensor to the wall box by inserting screws into the
two wide holes on the top and bottom of the attached metal
bracket. Match them up with the holes in the wall box and
tighten.
Passive Infrared 0-10 Volt Wall Switch Occupancy Sensor
CAUTION
PW-311 / PW-311-347
Interrupteur mural 0 – 10 Volt avec détecteur
de présence à infrarouges passif
Sensor de ocupación con interruptor de pared y
tecnología de infrarrojo pasivo de voltaje 0 a 10
SPECIFICATIONS
Voltages:
PW-311 ............................................ 120/277 VAC, 50/60 Hz
PW-311-347 ........................................... 347 VAC, 50/60 Hz
Load Limits:
@120 VAC . 1000-W tungsten ballast, E-ballast, LED, 1/4 HP
@277 VAC ............. 1200-W ballast, E-ballast, LED, 1/4 HP
@347 VAC ................................1500W ballast, LED, 1/4 HP
Time Delay Adjustment ....................................... 3 to 30 minutes
Walk-Through Mode ...........3 minutes if no activity after 30 sec.
Test Mode .................................. 10 min. with 10-sec. time delay
PIR Adjustment .........................................................High or Low
Light Level Adjustment ............................................ 8fc to 180+fc
Alerts Selectable Audible & Visual
Optional Neutral ..........................................................All models
Multi-Way Capability ...................................................All models
Terminal screw torque ................................ 16 lbf-in (18 kgf-cm)
High Trim ......................................................................... 6 to 10 v
Low Trim............................................................................ 0 to 4 v
Ramp Up .............................................................. 1 to 10 seconds
Fade Down ........................................................ 2.5 to 30 seconds
4. Turn the circuit breaker ON. Wait one minute, then push the
Auto ON/OFF switch for each load and the lights will turn ON.
There is a delay due to initial power-up of the sensor that
only occurs during installation.
5. Test and adjust the sensor if necessary.
6. Install industry standard decorator wall switch cover plate
(not included).
PW-311 and PW-311-347 Wiring
0-10V
Dimming
Violet
Gray
Black
Line
Green
Ground
Neutral
OPTIONAL
NEUTRAL WIRING
For applications
requiring neutral
wiring, remove tab
as shown to expose
terminals for wiring.
#12 – #14 AWG
Yellow
Cu Wire Only
Red
Load
White
(optional)
8" ying leads for
line, load, ground
and multi-way
connections
Red
Black
Optional neutral
Breakaway
terminals behind
tab
breakaway tab
Strip Gage
1/2"
12.7mm
Grey
Violet
Yellow
Green