IU errors
If the indoor unit generates an error, Aidoo Pro will communicate this to the BACnet platform.
This object is read only.
Digital input
Aidoo Pro will communicate the status of the digital input. This object is read only.
EN
Auxiliary heat
Aidoo Pro will communicate the status of Auxiliary heat. This object is read only.
Set-point temperature
The indoor unit set point temperature and its value are communicated to the BACnet system
and can be modified by the BACnet system. This parameter is read and write.
Room temperature (Localtemp)
The BACnet platform can obtain the room temperature of any zone. This object is read only.
Operation mode
Aidoo Pro will communicate the operation mode of the system or of each zone (depending on
the connected system), represented by a number. These are read/write objects. The modes are
as follows:
0 → Stop
2 → Cooling
3 → Heating
4 → Dry
6 → Ventilation
Speed
This parameter refers to the AC unit's fan speed. Aidoo Pro will communicate the speed of the
system or of each zone (depending on the connected system), represented by a number. These
are read/write objects.
Slats
Aidoo Pro will communicate the position of the slats represented by a number. These are read/
write objects. The position goes from 1 to 9; 10 is Swing mode.
Errors
If the indoor unit generates an error, Aidoo Pro will communicate this to the BACnet platform.
This object is read only.
8