9.12.2
How to switch off the dryer
Switch it off using the ON-OFF switch (position 1 paragraph 9.1).
9.12.3
How a service warning / alarm is displayed
A service warning / alarm is an unusual event that must recall the attention of the operators / maintenance technicians. It does not stop the
dryer.
Service warnings / alarms are automatically reset as soon as the problem is solved.
NOTE: the operator / maintenance technician must inspect the dryer and verify / solve the problem that generated the service warning.
Display 1st (left) and 10th (right) led are flashing
Display 10th (right) led is flashing
Display 1st (left) led is flashing
9.12.4
How is controlled the condenser fan (ADS 10-100)
A temperature probe T2 is located on the discharge side of the condenser. The condenser fan is activated (ON) when the T2 temperature
is higher than FANon setting (standard 35°C / 96°F) and led
Condenser fan stops at T2 temperatures 5°C / 10°F lower than FANon setting (standard 30°C / 86°F).
9.12.5 How is controlled the drain solenoid valve
Drain solenoid valve is activated (ON) for Ton seconds (standard 2 seconds) every Toff minutes (standard 1 minute).
Led
shows that condensate drain solenoid valve is ON.
The condensate drain test is always active using the button
9.12.6 6 How to change the operating parameters – SETUP menu
The setup menu can be used to change the dryer's operating parameters.
Only qualified personnel must be allowed to access to the setup menu. The manufacturer is not responsible for malfunctioning or
failure due to modification to the operating parameters.
With dryer ON press button
Access to the menu is confirmed by led
Keep
Set
pressed and use arrows
Press shortly
to skip to following parameter.
Set
Press
to exit setup menu (if no button is pressed after 2 minutes the menu is exited automatically).
Display
Synchronous flashing
led
ON
+ led
Synchronous flashing
led
ON
+led
Non-Synchronous flashing
led
ON
+led
NOTE : parameter values are displayed on the 10 led display where 1st (left) led is the lowest limit and 10th (right) is the highest limit.
Service Warning / Alarm
Led
is flashing
for at least 3 seconds to enter the setup menu.
Set
and
ON
to change the value. Release the button
Description
(AMD 10-100)
FANon : condenser fan activa-
tion (ON) temperature
Ton – drain time ON : time ON
condensate drain valve
ToF - drain time OFF : pause
time for condensate drain valve
Failure T1 (DewPoint) temperature probe.
Failure T2 (fan control) temperature probe.
NOTE : fan is forced always ON.
TABLE 9.1
is ON.
flashing (first parameter of menu).
Limits
31 ... 40°C or 88 ... 104ºF
1 ... 10 seg.
1 ... 10 min.
TABLE 9.2
65
Description
(ADS 10-100)
DewPoint too high
DewPoint too low
(lower than -1°C / 30°F).
to confirm the value.
Set
Resolution
1°C or 2°F
1 sec.
1 min.
Standard setup
35 or 96
2
1