DATA SHEET
ADMITS ALL TYPES OF PULSE SENSORS
WIDE FREQUENCY RANGES (down to 0.01Hz)
HIGH PRECISION AND STABILITY
DOUBLE ISOLATED OUTPUT (0/4-20mA, 0-10V)
ISOLATED POWER SUPPLY 20V - 250V AC/DC
PROGRAMMABLE CUTTING FREQUENCY (LOW CUT- OFF)
DESCRIPTION
Universal isolator converter for all types of pulse sensors.
Converts the frequency (tachometer) into a proportional and isolated signal in the form of current or voltage
It admits a wide frequency range, specialized in very low frequencies from 0 / 0.01Hz to 0 / 100kHz, configuring very
easily by means of numerical rotaries on the front, being protected by a hinged cover.
It incorporates a very useful selectable filter to stabilize low frequency signals.
Voltage (0 -10 V) / current (0/4 - 20 mA) outputs protected against polarity inversion and short circuit.
It has universal power supply 24 - 230 V AC/DC with wide margins
The connection is made by means of plug-in terminals, they facilitate the rapid exchange of modules without the need
to rewire and protect against mistakes.
It is protected by meeting EMC standards for industrial applications.
CONFIGURATIONS
INPUT SENSOR TYPE SELECTION
PROGRAMMING RANGE: 0-1 KHz <> 4-20 mA
FREQUENCY RANGE
START OF
END OF SCALE
SCALE
Fixed to
—
QUICK INSTALLATION GUIDE
DIGITAL FREQUENCY CONVERTER
START OF SCALE ≠ 0 : origin is not 0
Example for an initial scale value other than 0hz. Range : 1-5Hz <> 4-20mA
(START OF SCALE) Put the left scale start microswitch up in the START position >0 XHz
Set the start of scale value with the 3 rotaries. Example 01x1 (1Hz)
Turn on the equipment having previously pressed the programming button PROG. The led flashes slowly at
first and then quickly to signal that this value has been saved.
TURN OFF THE DEVICE.
(END OF SCALE) Numerically place the END of scale value with the 3 rotaries. Example 05x1 (5Hz)
TURN ON THE EQUIPMENT and it would already be working with the fixed led indicating that everything is
correct
CUTOFF FREQUENCY (Fc) :
POWER SUPPLY OK
To set an Fc of 1Hz. Range : 0-5 Hz <> 4-20 mA (4mA from 0 to 0.99Hz)
OPERATION DESCRIPTION: CONSULT.
TEST MODE : Allows you to see the value of START SCALE or Fc.
The numerical rotary switches indicate the full scale value of the programming.
OPERATION DESCRIPTION: CONSULT.
ADVANCED MODE
The origin is zero but the output is maintains
0V/4mA below the value of Fc.
6
KOS1600FA