I N S T A L L A T I O N I N S T R U C T I O N S
Wiring the AG-4200 in a Conventional HVAC System
To ensure proper performance of product, instructions must be followed.
1. Double check that the power is disconnected to the unit at the main panel prior to moving to step 2. Refer to the
appliance manufacturer's installation and operating instructions and also review wire layout in the instructions.
2. Locate the red wire coming from the 24 volt thermostat "R" terminal.
3. Disconnect or cut red wire. Connect the Normally Closed non-ribbed wire of the switch, using a wire nut, to
the thermostat side of the circuit. Connect the Common ribbed wire of the switch, using a wire nut, to the air
handler side of the circuit or to terminal in unit. Incorporating both switch wires in the red circuit will shut the unit
completely off.
4. Test the switch. (At start-up, check initial amperage load.)
a) With unit on, test switch by pulling the float pin up. (fig. 8) Unit should stop running if switch is correctly wired.
b) To test switch responsiveness, fill pan with water to ensure that the switch stops the unit before the pan
overflows. Remove water.
5. Place the WARNING sticker on unit in a clearly visible location. (fig. 9)
check
float tab
6. For wiring the normally open third wire (short wire) refer to the following diagrams:
Standard HVAC installation
w/optional external alarm or accessory
Thermostat
C
R
NC-Non-Ribbed
Common-Ribbed
NO-Short wire
(If not used, wire nut and tape)
Wiring the AG-4200 in a Communicating HVAC System
1. See equipment manufacturer's recommendations for specific wiring instructions.
Limited Warranty
For more information on our product limited warranty, visit RectorSeal.com
24 Volt AC, 5 Amp, GP, Use in CLass 2 (Thermostat) Circuit Only
Manufactured by
RectorSeal, LLC
2601 Spenwick Drive  Houston, TX 77055, USA  800-231-3345  Fax 800-441-0051 
A CSW Industrials Company. RectorSeal, the logos and other trademarks are property of RectorSeal, LLC, its affiliates or its licensors and are protected by copyright, trademark
and other intellectual property laws, and may not be used without permission. RectorSeal reserves the right to change specifications without prior notice. ©2023 RectorSeal. All
rights reserved. R50963-0123
Page 2 of 4
(fig. 8)
24Vac transformer
24Vac common
24Vac hot
AG 9100
White
Remote alarm
slide tab up
to test switch.
Unit will shut
off if correctly
Unit is equipped with an AquaGuard condensate
wired.
shut-off switch. If A/C unit is not operating, check
for condensate in drain pan or tray. Inspect,
clean and test the device every 30 days and
(fig. 9)
Optional HVAC installation for breaking Compressor Yellow wire
w/optional external alarm or accessory
Thermostat
C
Y
Common-Ribbed
NC-Non-Ribbed
NO-Short wire
(If not used, wire nut and tape)
AQUAGUARD
Water Sensor & Drain Port
following each cleaning of the drain line.