Timer box IV
P7 - Choose between 0-10V or PWM pulse wide modulation. (default is 0-10V)
P8 - Maximum value of the output signal. Set here the maximum value of the
output signal to your dimmable ballast or LED light. (This value can not be set
lower as the P9 minimal value +10%)
P9 - Minimal value of the output signal. Set here the minimal value of the output
signal. This value usually is set in the way that the dimmable ballast of the LED
EN
Lamp doesn't switch off. (This value can not be greater than P8 -10%)
P10 - At the moment the timer switches on the lights you can set a dim-function
Sunrise in minutes. The output signal will increase his value from P9 minimal
dimming value until P8 maximal dimming value during this time.
P11 - The opposite of P9 Sunset here you can set the time the output signal will
reduce from P8 maximal dimming value to P9 minimal dimming value before the
timer switches off.
P12 - Choose if you want to reset the controller to factory settings.
P13 - END chooses to exit the sub settings and return to the main screen.