Installation Instructions – CBRK Emergency Battery Packs
Important Safeguards
WHEN USING ELECTRICAL EQUIPMENT, BASIC SAFETY
PRECAUTIONS SHOULD ALWAYS BE OBSERVED INCLUDING
THE FOLLOWING.
1.
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
2.
Do not use outdoors.
3.
Do not mount near gas or electric heaters.
4.
Equipment should be mounted in locations and at
adequate heights to prevent tampering by unauthorized
personnel.
5.
The use of accessory equipment not recommended
by Cooper Lighting Solutions may cause an unsafe
condition and will void the warranty.
6.
Do not use this equipment for other than its intended
purpose.
7.
Not for use with sealed and gasketed fixtures.
8.
SAVE THESE INSTRUCTIONS.
Notes
1.
To prevent voltage from being present on the output
wires (Red/White & Blue/White), do not connect the
test button assembly to the EBP or Ensure the EZ key is
securely in place.
2.
This product is for use with LED fixtures that have LED
loads capable of the output wattage and LED forward
voltage within the ranges below.
Output
Power (W)
All 14-Watt
14
Versions
Table 1
3.
Make sure all the connections are in accordance with
the National Electrical Code and any local regulations.
4.
To reduce the risk of electrical shock, disconnect both
normal and emergency power supplies and the test
button indicator light (which disconnects the battery)
before servicing. Ensuring the battery disconnect
is securely in place also prevents battery powered
operation.
5.
These emergency ballasts can be field, or factory
installed depending on version. See mounting section
for details.
6.
An un-switched AC power source is required.
(120 - 277 volts 50/60 HZ) for proper operation.
7.
Do not attempt to service the battery. The sealed,
no-maintenance battery is not field replaceable. Contact
the manufacturer for information on service.
8.
All maintenance should be performed by qualified
service personnel.
2
COOPER LIGHTING SOLUTIONS
Min Vf (V)
Max Vf (V)
16
55
IB519148EN
Installation instructions
Features
This emergency battery pack (EBP) includes extra features
which enhance its operation and maintainability.
1.
Patented EZ key battery disconnect: When the EZ
key is inserted into the test button, the battery is
disconnected. This feature prevents unnecessary
cycling of the battery during the construction process.
It can also be used if the room is decommissioned for
an extended period to prevent the batteries from being
overdischarged.
2.
Patent pending test button / indicator light / laser
input: The test button houses the EZ key, powers the
indicator light, contains the laser input for testing and
functions as the mechanical test button. Integration
of these functions improves performance and fixture
aesthetics.
3.
Power controlled output: This feature maintains
consistent light output during the entire 90 minutes of
emergency operation ensuring there is no drop in lumen
output as the battery voltage drops.
Field Installation Classification
(EBPLED14W)
1.
Determine electrical compatibility with fixture: Verify
the emergency driver wattage (14 watts depending on
model) does not exceed the driver's AC input. Also,
verify that the forward voltage of the LEDs is within the
operating parameters of the selected model
(see Table 1).
2.
Calculate lumen output during emergency operation:
Go to the website www.designlights.org and identify
the light fixture by using the available search criteria.
Determine the fixture efficacy in lumens/watt. Multiply
the fixture efficacy by the output wattage of the
selected emergency battery pack to determine the
lumen output of the fixture during emergency operation.
Example: Fixture efficacy = 100 lumens/watt
EBPLED14W provides 14 watts of constant
power
Fixture output = 100 lumens/watt X 14
watts = 1400 lumens during emergency
operation
3.
Ensure means of egress lighting levels: Follow industry
standard methods of lighting layout to determine
placement of emergency battery pack equipped
fixtures. Verify the selected EBP will provide enough
lumen output to meet path of egress illumination
requirements.