Installation (continued)
3
Make the electrical
connections
If necessary, strip 3/8" of insulation from junction
box and lighting fixture wires (fig 8).
Standard Non-Dimming Wiring diagram
(Follow these steps when NOT wiring to a 0-10V dimmer)
Connect light fixture black wire to junction box
black wire (line), light fixture white wire to
junction box white wire (common), and the light
fixture green wire to the junction box ground
wire (fig 9).
For the purple and pink unused fixture
wires either leave the wires unstripped or install
wire nuts (BB) on the ends to prevent electrical
hazard (fig 9).
NOTICE: Leave purple and pink wires terminated
with wire nuts installed and separated when NOT
connecting to a 0-10V dimmer. DO NOT connect the purple
and pink wires to any other wires unless wiring to a
0-10V dimmer designed for use with LED light fixtures (fig 9).
TIP: Hold stripped ends near each other and align any
frayed strands (do not twist wires). Push the wires into
wire nuts (BB) and use your fingers to twist the wire nuts
clockwise until tight. Check for tightness by pulling wires.
(fig 8).
Pink
(fig 9).
For electrical wiring to 0-10V Dimmer
(Follow these steps when wiring to a 0-10V dimmer)
Connect light fixture black wire to junction box
black wire (line), light fixture white wire to junction
box white wire (common) and the light fixture green
wire to junction box ground wire.
For dimming, when wiring to a 0-10V dimmer,
connect the light fixture purple wire to the dimming
device wire (+DIM) and the light fixture pink wire to
the dimming device wire (-DIM) (fig10).
(fig 10).