INSTALLATION
Physical Installation
Mount the alarm panel within 5 feet of a 120 VAC, 50/60 Hz electrical
outlet using two #6 self-tapping screws (not included).
NOTE: Also use #8 plastic anchors if mounting to sheet rock.
Battery Backup Installation (Optional)
1. Remove the cover.
2. Install a 9 VDC battery (not included).
3. Press Alarm Test to ensure that the alarm sounds and the battery
backup system is working.
• Alarm LEDs, alarm buzzer, and auxiliary contacts will activate.
NOTE: When on battery backup, the green power LED will not light up.
4. If not using auxiliary contacts for an existing alarm security system, reinstall the access cover.
Electrical Connections
1
1A
2A
1. To connect the alarm panel into an existing BAS or alarm system, use 18 gauge 2 conductor wire.
NOTE: Normally open dry contacts can switch 24VDC, 500mA maximum.
2. To connect the alarm to the OA1S control panel, use 18 gauge 4 conductor wire to connect the OA1S
control panel to the alarm panel.
• The control panel's exact terminal style may vary, but C, O, W, T is consistent.
NOTE: Normally open or normally closed contacts can switch 9-10VDC, 200mA maximum.
3. Run the wires through the wiring access hole.
4. Replace the alarm panel cover.