Atmor will not be liable for any damages because of failure to comply with the installation and operating instructions outlined in this manual or because of improper use. Improper use includes the use of this appliance to heat any liquid other than Failure to comply with the installation and operating instructions or improper use voids the warranty.
Technical Information Circuit breaker Required wire Model *Wattage Voltage Amperage Phase size size AT900-03 3 kW 10 AWG AT900-04 3.8 kW 12 AWG AT900-06 6.5 kW 10 AWG AT900-08 8.5 kW 6 AWG AT900-10 10.5 kW 6 AWG AT900-13 13 kW 4 AWG Minimum water flow to activate unit: 0.5 GPM Nominal water volume: 0.11 gal (0.42l)
Página 4
Assembly Instructions 1. Mount ground plate to wall. Connect the Pressure Relief Device Remove the appliance covers 2. Pull wires through. (PRD) to the unit (Fig1) Note: (Figure 2). 3. Cut out hole in back of unit IMPORTANT – do not discard (Right/Left back) and pass this step.
Página 5
Rubber Cold G = Green or Yellow N = White L1/L2 = Black L1 L2 *3a) *3b) *3c) Note: Neutral (N) does not need to 3.5-8.5kW 8.6-13kW be connected. G L1 (L2)
Página 6
Connect the power cable to the terminal block. Caution: The heater must be grounded. Reference figure *3 on page 4 and Run the water flow for Electrical diagram on page 6 one minute to check for leakage before connecting to power. Reattach the front cover of the heater and secure it with 4 screws and then slide the bottom gray cover...
Operation Guide Medium High MODEL AT900-03 AT900-04 AT900-06 AT900-08 AT900-10 5.25 5.25 10.5 AT900-13 Troubleshooting PROBLEM ISSUE POSSIBLE CAUSE SOLUTION Water not hot Too much water flowing Reduce the flow rate of the water via enough. through the heater. the outlet tap. Reduction in the ambient Switch to higher temperature setting.
Página 9
Troubleshooting PROBLEM ISSUE POSSIBLE CAUSE SOLUTION Water too hot. Not enough water flowing Increase the flow rate via the outlet through the heater. tap. Increase in the ambient Switch to lower temperature setting. temperature. Heater shut off Interruption of main Check incoming power supply, MCB, during use.
Página 10
Parts 1. Switches 2. PRD 5. Hot water outlet (to be connected to the main hot 3. Cold water inlet water pipe)
Página 12
LIMITED WARRANTY Atmor warrants to the original owner that our instant water heaters will be free from defects in workmanship and material for a period of TWO YEARS from the date of purchase, and free from leakage for a period of SEVEN YEARS from the date of purchase. Should any part(s) prove to be defective during this period, Atmor will be responsible for replacement of the defective part(s) only.
Página 13
Hot Water on Demand Instalación y guía de funcionamiento Serie InLine 900 3kW-13kW www.atmor.net...
Atmor no será responsable de los daños ocasionados por no cumplir las instrucciones de instalación y funcionamiento detallados en este manual o por el uso inadecuado. El uso inadecuado incluye el uso de este artefacto para calentar cualquier líquido que no sea agua.
Instrucciones de ensamblaje 1. Instale la placa de tierra a Conecte el dispositivo de alivio de Retire las cubiertas del la pared. presión a la unidad (Fig. 1). artefacto (Figura 2). 2. Jale los cables. Nota: IMPORTANTE – No omita este paso.
Goma Dispositivo de alivio de presión Frío Caliente G = Verde o amarillo N = Blanco L1/L2 = Negro L1 L2 *3a) *3b) *3c) Nota: el neutro (N) no requiere 3.5-8.5kW 8.6-13kW conexión. G L1 (L2)
Página 18
Conecte el cable de alimentación al bloque de terminales. Precaución: el calentador debe estar conectado a tierra. Consulte la figura 3 en la página 4 y el Deje correr el agua durante un diagrama eléctrico en la página 6. minuto para verificar si hay fugas antes de conectar el artefacto al suministro eléctrico.
Guía de funcionamiento Bajo Medio Alto MODELO AT900-03 AT900-04 AT900-06 AT900-08 AT900-10 5.25 5.25 10.5 AT900-13 Resolución de problemas PROBLEMA CAUSA POSIBLE SOLUCIÓN Fluye demasiada agua por Reducir la tasa de flujo del agua El agua no está lo el calentador. mediante la llave de salida.
Página 21
Resolución de problemas PROBLEMA CAUSA POSIBLE SOLUCIÓN El agua está No fluye suficiente agua por Incrementar la tasa de flujo mediante la demasiado caliente. el calentador. llave de salida. La temperatura ambiente Cambiar a un ajuste de temperatura aumentó. más bajo. El calentador se Interrupción del Revisar el suministro de energía,...
Página 22
Piezas 1. Interruptores 2. Dispositivo de alivio de presión 5. Salida de agua caliente (para conectar a la tubería 3. Entrada de de agua caliente) agua fría...
Si el propietario desea devolver el calentador para su reparación, el propietario primero debe obtener una autorización escrita de Atmor. Se requiere que el propietario muestre una prueba de la fecha de compra y pague todos los costos de transporte para devolver la pieza defectuosa o el calentador para su reparación o reemplazo.