DST DR-31 T10 Manual Del Usuario página 12

Deshumidificador desecante

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

EN
4.5 WET AIR OUTLET
Install a damper on wet air outlet to adjust the electric consumption during free blowing operation. Other models may require a damper to prevent from overloading during
free blowing operation.
It is recommended to adjust damper so that the electric consumption on the ammeter displays the nominal current stated in the technical data.
See heater current in
.
4.6 HUMIDISTAT/ELECTRONIC CONTROLLER INSTALLATION
Install the humidistat/electronic controller away from the dry air out path to avoid false readings.
4.7 ELECTRICAL CONNECTION
Electrical components should be connected to the supply according to the local regulations and requirements.
4.7.1 POWER SUPPLY
The single-phase cable is to be directly connected to the power grid with earthing capability.
See electrical diagram for a electrical voltage and operation frequency.
4.7.2
breaker (EN 60898-1).
4.7.3 HUMIDISTAT CONNECTIONS
See electrical diagram for connections.
Seibu Giken DST
12
DR-31 T10 EN.05