LOAD LEVEL STATUS
Requests the load level, expressed as percentage of maximum.
Send Query to UPS: ?LOADSTAT<CR>
Action: Load level will be displayed
Response: $LOAD = xxx<CR>
xxx is the load level (percentage of maximum load) expressed in decimal
format. If the value is less than 100, the hundreds digit is
represented with a 0.
BATTERY LEVEL STATUS
Requests the battery level, expressed as a percentage of maximum (full
charge).
Send Query to UPS: ?BATTERYSTAT<CR>
Action: Load level will be displayed
Response: $BATTERY = xxx<CR>
xxx is the battery charge level (percentage of maximum charge) expressed in
decimal format. If the value is less than 100, the hundreds digit is represented
with a 0.
LIST CONFIGURATION
Requests a list of all configurable parameters and current settings.
Send Query to UPS: ?LIST_CONFIG<CR>
Action: List of configurable parameters and current settings will be displayed.
Response: $BTHRESH = level<CR>
$BUZZER = mode<CR>
$AVR = mode<CR>
$FEEDBACK = mode<CR>
$LINEFEED = mode<CR>
$BRIGHTNESS = xxx<CR>
$SCROLL_MODE = xxx<CR>
$SLEEP_MODE = xxx<CR>
VOLTAGE
Requests the input voltage level.
Send Query to UPS: ? VOLTAGE <CR>
Response: $ VOLTS-IN = v v v <CR>
v v v is the input voltage.
CURRENT
Requests the output current.
Send Query to UPS: ? CURRENT <CR>
Action: send Query to UPS: ? CURRENT <CR>
Response: $ CURRENT = c c c <CR>
c c c is the output current in amps.
LIST OF ALL COMMANDS AND QUERIES
Send Query to UPS: ?HELP<CR>
Action: List of all commands and queries will be displayed
Response:
!ALL_ON<CR>
!ALL_OFF<CR>
!SWITCH<CR>
!SET_BATTHRESH<CR>
!SET_BUZZER<CR>
!SET_AVR<CR>
!SET_FEEDBACK<CR>
!SET_LINEFEED<CR>
!RESET_ALL<CR>
!SET_BRIGHT<CR>
RESPONSES & MESSAGES OUTLET STATUS CHANGE CONDITION
RESPONSE
Outlet Bank 1 changes state $BANK1 = status<CR>
Outlet Bank 2 changes state $BANK2 = status<CR>
Outlet Bank 3 changes state $BANK3 = status<CR>
Outlet Bank 4 changes state $BANK4 = status<CR>
status = {ON, OFF}
POWER BUTTON STATUS CHANGE CONDITION RESPONSE
Power Button changes ON/OFF status $BUTTON = status<CR>
status = {ON, OFF}
POWER FAULT STATUS CHANGE CONDITION RESPONSE
Overvoltage State
Undervoltage State
Lost Power State
Test Mode
Recovery Mode
Normal Operation Mode
Low Battery
AVR Stage
Remaining Backup Time
Battery State
Power Control Software
Complete Instructions are available by clicking on Help on the Power
Control Software welcome screen
11
!SET_SCROLLMODE<CR>
!SET_SLEEPMODE<CR>
?ID<CR>
?OUTLETSTAT<CR>
?POWERSTAT<CR>
?VOLTAGE<CR>
?LOADSTAT<CR>
?BATTERYSTAT<CR>
?LIST_CONFIG<CR>
?HELP<CR>
$PWR = OVERVOLTAGE<CR>
$PWR = UNDERVOLTAGE<CR>
$PWR = LOST POWER<CR>
$PWR = TEST<CR>
$PWR = RECOVERY<CR>
$PWR = NORMAL<CR>
$LOWBAT<CR>
$AVRSTATE = state<CR>
state = {BOOST, BUCK}
$TIME = xxx<CR>
xxx = backup time
$BATTSTATE = xxx<CR>
xxx = {CHARGE, DISCHARGE, FULL}