53004
AS2473.2 (Australia)
Connection:
• Model # 53001: CGA580 (US)
• Model # 53002: DIN477#6 & DIN477#10 (includes adapter to convert
DIN477#6 to DIN477#10 (France/Germany)
• Model # 53003: BS3 (England)
• Model # 53004: AS2473.2 (Australia)
• Model # 53005: 5-UNI11144 (Italy)
• Model # 53006: 21.8 L NEN 3268 left hand thread, for Hydrogenated Nitrogen
Pressure Regulator:
• 100 - 4500 PSI (7 - 300 Bar) High side
• 30 – 1000 PSI (2 – 70 Bar) Adjustment range
• Integrated Shutoff Valve
Safety Relief Valve: 725 PSI (50 Bar)
Gauge Diameter: 2 5/8 (68 mm) Not including guard
WARNINGS
• Only use with nitrogen gas (N2).
• The regulator is not to be used with liquid nitrogen.
• Do not modify the regulator. Doing so could result in personal injury.
• Do not over-pressurize the regulator. This could cause leakage, part damage or
personal injury due to bursting of pressure-containing parts.
• Keep the regulator clean and free of oil.
• Do not use a damaged regulator. Except for replacing the gauges, do not
attempt to repair the regulator.
• Failure to follow instructions can result in personal injury and/or damage to the
equipment.
• Do not install this regulator where service conditions can exceed the
specifications of any applicable local, state, or federal codes and regulations.
• Wear safety glasses and gloves.
REGULATOR CONNECTION AND USE
Note: The nitrogen regulator can be used with a charging hose and leak testing gauge
assembly or a charging and testing manifold.
• Make sure the cylinder connection (1) is clean and free from damage.
• Turn the T handle (6) all of the way out (counter clockwise, looking from the bottom).
• Open the output control valve (4) to release any pressure, and then close it.
• Install the nylon gasket or O-ring, if the connection requires one.
• Install the regulator onto the cylinder. Do not over tighten the nut on gasket
connections.
• Connect the yellow charging hose (11) from the regulator to the leak testing gauge
assembly, making sure the ball valve connection (9) is closed.
(If using a manifold, connect the yellow charging hose (15) of the manifold to
the regulator.)
• Connect the other end of the leak testing gauge assembly (8) to the system.
(If using a manifold, connect the low side hose (14) from the manifold to the system.)
• Slowly open the cylinder valve. The high side gauge (2) should read the
cylinder pressure.
• Adjust the regulator pressure by turning the T handle (6) clockwise until the required
pressure (based on the system's refrigerant) is shown on the low side (output) (3)
pressure gauge.
NOTE: This is a non-reliving regulator. To adjust the output pressure lower, some nitrogen
will have to be released from the output (e.g. with no hoses connected, turn the T handle
counter-clockwise, then open the output control valve and close it. The output gauge
should read a lower pressure.)
• If using the leak testing gauge assembly, turn the red needle to the required
53005
5-UNI11144 (Italy)
www.mastercool.com
53006
21.8 L NEN 3268 left hand
thread, for Hydrogenated
Nitrogen
3