Error 1: Thermostat (wired) - Aidoo
This issue does not allow control of the zone. To resolve this issue, make the following checks:
1.
Status of the main control board: Check that the power supply is correct.
2.
Status of the main control board: Correct operation of LEDs.
3.
Connections: Check that the polarity of the connections to the Aidoo and the thermostat is
EN
correct.
Wired: Check that the voltage between poles (A /-) and (B/-) is 1.8 VDC.
4.
5.
Restart the zone and reassociate it to the system:
•
Blueface Zero thermostats: Press on the word Reset to restart the device. If the
error persists, press and hold the icon and reset the thermostat. Carry out the initial
configuration of the system.
Restart the system: If you restart the system, this error may appear on the thermostats due
6.
to the restart. This message should disappear in approximately 30 seconds once the restart
has been completed.