Descargar Imprimir esta página

Georg Fischer JRG 9950.020 Instrucciones De Montaje, Uso Y Mantenimiento página 21

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

EN
Connect Flow Sensor to Controller
The plug (3) of the Flow Sensor has to be connected to M8 plug (8) of the
Controller. If the Controller is situated at more than 1m from the Flow
Sensor, please use extension sensor cable (9943.005). The maximum
cable length from Flow Sensor to the Controller is 50m.
To achieve the greatest possible measuring accuracy, a straight inlet and
outlet section of the applicable nominal width (DN) must be used. The
length of the inflow section should at least be 10xDN and of the outlet pipe
5xDN.
Possibility of draining
Possibility of bubble formation with
draining
21

Publicidad

loading

Productos relacionados para Georg Fischer JRG 9950.020