During normal running
Current switch cabinet internal temperature TS1 (if two tempe-
rature sensors TS1 and TS2 are used these are displayed alter-
nately for 15 sec). The position at bottom right indicates whether
in °C or °F
When a system fault occurs
The highest value error number alternates with the temperature
from TS1 (switch cabinet internal temperature) or TS2
In menu mode
Display of the selected menu option or the current parameter
and information values
The temperature range of TS1 and TS2 in the display is from 0ºC to
+90ºC (+32ºF to +194ºF). If the temperature is below 0ºC (+32ºF) a
'u' appears in the display. At temperatures above +90ºC (+194ºF)
an 'o' appears in the display.

3. Use of the unit (menu structure)

Attention!
Default factory parameters may only be modified by
authorised individuals.
The menu is activated by pressing the 'MODE' button for at least 4
seconds while in operational display mode (normal operation) (see
also Figure 2). In this mode the unit stops all motors. The status of
the error message output remains unaltered in this case.
The menu consists of 3 levels, each of which contains a different
number of menu options. If no entry has been made for 60 seconds,
regardless of menu option, the unit changes automatically to
operational display, and normal operation is restarted.

3.1. Test mode (menu option 1, level 1)

Using this function, a function test of the unit can be carried out
regardless of the ambient conditions. Before executing the function
test, the coded number of the connected temperature sensors
recognised by the system is displayed for 30 sec. The number of
temperature sensors is coded as per Table 1.
This test is also carried out every time the cooling unit is connected
to the mains supply.
Display
T sensor 1
recognised
(control
sensor*)
't 0'
-
't 1'
x
't 2'
-
't 3'
x
Table 1: coding for number of temperature sensors
*Control sensor:
This temperature sensor is used to control
the switch cabinet internal temperature
Analytical sensor:
This sensor can be used for analytical pur
poses (e.g. temperature monitoring of spe
cific switch cabinet components and deter
mination of 'hot spots'), and can be sited by
the user as required.
Sequence
operational display
Display
Menu activation by pressing the 'MODE' button (3)
Action
for 4 sec.
085 505 518b
T sensor 2
Remarks
recognised
(analytical
sensor*)
No sensor
-
recognised
error condition
-
Only TS2
x
recognised
error condition
x
Display [tES] (test mode)
Display
Confirmation of menu option [tES] (test mode) with
Action
the 'SELECT' button (4)
Display [ttt] (flashing)
Display
Confirmation of menu option [ttt] (activate test) with
Action
the 'SELECT' button (4)
All motors are started and a self-test is run (30
Behaviour
sec.)
Display [t y] (y represents the number of recog-
Display
nised temperature sensors as per Table 1) for 30
sec.
Display [txx] (xx represents the display of the re-
Display
maining period of test running)
After the test mode has elapsed (30 sec.) the unit changes
automatically into normal mode. If errors occurred during the test
run, these are displayed alternately with the temperature.
3.2. Setpoints (menu option 2, level 1)
This menu option includes all parameters which affect the cooling
operation of the unit. The setting of the temperature setpoint T
and the alarm temperatures T
one another. Starting from the temperature setpoint, T
lower than (T
+ 10K). T
cannot be higher than (T
set
min
Example:
Switch cabinet internal temperature T
Range setting for T
max
Range setting for T
min
Range settings
Parameter
Min. value
T
25ºC/77ºF
set
T
±1
set
T
35ºC/95ºF
max
T
10ºC/50ºF
min
Table 2: Setpoint range settings
Sequence
Operational display
Display
Menu activation by pressing the 'MODE' button (3)
Action
for 4 sec.
Display [tES] (test mode)
Display
Selection of menu option 'SET-Points' in menu level
Action
1 with the „ " (5) and „ " (6) buttons
Display [SEt] (SET-Points)
Display
Confirmation of menu option [SEt] with the 'SELECT'
Action
button (4)
Display [t S] (temperature setpoint)
Display
Selection of parameters in menu level 2 with the
Action
„ " (5) and „ " (6) buttons
Confirmation of menu option in level 2 with the
Action
'SELECT' button (4)
Current parameter value (flashing)
Display
Modification of the parameter in menu level 3 with
Action
the „ " (5) and „ " (6) buttons
Confirmation of the new value in level 3 with the
Action
'SELECT' button (4)
New parameter value for 4 sec.
Display
Automatic return to the menu option above.
Behaviour
After all parameters have been set as desired, their acceptance
must be activated.
and T
are thereby dependent on
max
min
cannot be
max
– 10K).
set
= 35ºC
set
= 45ºC to 60ºC
= 10ºC to 25ºC
Max. value Step Function
Switch cabinet
50ºC/122ºF
1K
temperature
setpoint
Hysteresis
±5
1K
temperature
setpoint
60ºC/140ºF
1K
Max. alarm
temperature
40ºC/104ºF
1K
Min. alarm
temperature
set
9