recommended to adjust the "UFF" parameter rather than changing HU.
– ("StH") Setting of trip time of the harmonic distortion alarm t.h.d.
The possible settings are 1,2,3. If you set 1, the trip time will be
proportional to the level of harmonic distortion; setting 2 will double
this time; setting 3 will quadruplicate the time (you are advised not
to change this parameter).
– ("Adr") Instrument address for Rs485 network connection to other
instruments and a PC (this parameter is available only for seven-
and twelve-step versions of REGO).
– ("bdr") Speed of data transmission (Baud Rate) on the Rs485
port. The speed is expressed without the last zero (e.g. 9600bps is
shown as "960"; this parameter is available only for seven- and
twelve-step versions of REGO).
Press DATA for three seconds to exit the menu.