Airo GORBEA R32 Manual De Usuario E Instalacion página 53

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Installation Instructions
2. During the transportation of the outdoor unit, two lifting ropes long enough must be used
in four directions and the separation included angle must be less than 40° prevent the
center of unit deviating.
3. During the installation, M10 screws should be used to fix the support leg and base frame
of the unit.
4. The unit should be installed on a concrete base frame with a height of 10cm.
5. The installation space of the unit should be as required in Fig.5.
Installation Space Requirements of the Outdoor Unit:
>500
Connection between Indoor and Outdoor Units
● Energy level and Capacity Code of the Indoor and Outdoor Units
Table 5
Indoor Unit
Outdoor Unit
1. The outdoor unit with energy level 18 can drive up to two sets of indoor units, the outdoor
unit 24 can drive up to three, the outdoor unit 28/36 can drive up to four, while the outdoor
unit 42 can drive up to five.
2. The sum of the capacity codes of the indoor units should be among 50%-150% of that of
the outdoor unit.
>500
Energy Level
07
09
12
18
24
18
24
28
36
42
51
>1000
>2000
Capacity Code
Units: mm
>500
Fig.5
23
26
35
52
71
52
71
82
100
120

Publicidad

Capítulos

Tabla de contenido

Solución de problemas

loading

Este manual también es adecuado para:

Gorbea 2x1Gorbea 3x1

Tabla de contenido