5.3 Mechanical mounting

The maximum torque depends on the mounting location (e.g. material and shape). If you have
any questions, please consult our application advisor.
→ For contact information, see chapter 1 "General" or the rear side of the operating instructions.
1.
Seal sealing surface (→ see "Sealing variants").
2.
Tighten the pressure switch in the mounting location by hand.
3.
Tighten via spanner flat using torque wrench.
Sealing variants
Cylindrical thread
Seal sealing surface 1 with flat seal,
sealing lens or profile seal.
Conical thread
Wrap sealing material around thread
(e.g. PTFE band).
5.4 Electrical mounting
5.4.1 Requirements on voltage supply
→ For auxiliary energy, see type label
The pressure switch must be supplied by an energy-limited circuit as per 9.4 of the UL/EN/
IEC 61010-1 or LPS as per UL/EN/IEC 60950-1 / CSA C22.2 No.60950-1 or class 2 as per
UL1310 / UL1585 (NEC or CEC).
O P E R A T I N G I N S T R U C T I O N S P B S p l u s
4 4
5. COMMISSIONING, OPERATION
according to EN 837
NPT, R and PT
according to DIN 3852-E