Operating Instructions
Warning
ATT5
ILOC
OL
PAS
UL
Error
ERR
ERR1
ERR2
SC
Confirm warnings and errors with confirmation pushbutton.
O P E R A T I N G I N S T R U C T I O N S P B S p l u s
5 6
6. FAULTS
Description
Maximum turn down exceeded
Menu locked by IO-Link
Overload pressure, measuring range exceeded > about 3.125% (digital display flashes)
Request for password entry
Underload pressure, measuring range undercut < about 3.125% (digital display flashes)
Description
Internal error (device restart or reset to factory setting could help)
The analog output controls the alarm signal ≤ 3.6 mA (4 ... 20 mA output signal) or
≥ 11 V (0 ... 10 V output signal) in accordance with NAMUR43
The switching outputs maintain the current switching state (output open or closed)
Device temperature exceeded/undercut or auxiliary energy undercut
The analog output is output. There are limits regarding accuracy (influence of tempera-
ture) and maximum analog value (auxiliary energy undercut)
The switching outputs maintain the current switching state (output open or closed)
Sensor defect detected, check whether high overload pressure exists (can be detected
as sensor defect), a device restart or device exchange may be necessary
The analog output controls the alarm signal ≤ 3.6 mA (4 ... 20 mA output signal) or
≥ 11 V (0 ... 10 V output signal) in accordance with NAMUR43
The switching outputs maintain the current switching state (output open or closed)
Short-circuit on switching output 1 or 2 detected
The affected switching output is deactivated as long as the short-circuit exists
PBS plus
8024946 | SICK AG
Subject to change without notice