(*)Depending on which side the motor 1 and motor 2 are placed the
red and blue wires of each motor must be interchanged.
In the circuit there are light indicators (4 LED) behind the motor
connections. The door should open when the green indicator light
comes on and close when the red light comes on. Swap the brown
and blue wires if the door closes when it should open and open
when it should close.
The output for the blinker is active during the entire maneuver
(included with the door open) and deactivated 1 minute after
finishing the closing.
4.2 Control connector
½ (COM)
P.SW CL OP
P.SW
15V (+ -)
IR (COM)
COM
+PWR (COM)
Contact inputs ½ IR +PWR use COM as second connection.
If photocell is not installed a wire bridge must shortcircuit IR and
COM.
4.3 Photocell
The photocell is a device that detects obstacles.
It consists of an emitter and an infrared receiver, which are located
on the sides of the door. When the infrared beam is cut, and does
not reach the receiver, an obstacle is detected.
8
Single leaf open/close contact
Open / close contact
Close contact
15 V. accesories power output
Photocell N.C contact
Signals common
24 V. accesories power output