On/Off heating key (2) and LED display heating (3) work exactly the same as in the
manual mode.
BMS: Circuit board is equipped with a BMS input (floating contact) (25) and with a
BMS output (floating contact) (21).
BMS input/external release: The air curtain system runs in normal operation if the
BMS input (floating contact) (25) is electrically closed. If it is electrically opened then
the air curtain system (fan output (230VAC) (17) as well as the heating output (230
VAC) (15) is switched off and the red LED display fan step (5) flashes beside the "0"
symbol.
BMS output/operating message: If the air curtain system (the fan output (230VAC)
(17)) is switched on then the BMS output (floating contact) (21) is likewise activated
(contact closed).
Frost protection input: If the frost protection (floating contact) (23) is opened then the
heating is connected, the air curtain system (fans) is switched off and the LED display
frost protection (7) shines.
Thermal contact motors: The thermal contact function is activated and de-activated
via the DIP function selection switch SW1-3 (20). If the DIP switch is positioned on
ON, the function is activated. When the function is deactivated the thermal contact
motor is ignored.
The LED display (6) shines during release of a thermal contact in the motor.
Slave mode
The Slave mode is selected via the DIP function selection switch SW1 (20). In Slave
mode the air curtain system is operated in the speed provided by the Master unit.
11