5.2 Loss of head

Pressure loss water side
60
50
40
30
20
10
0
2000
2500
3000
fig. 20 - Pressure loss
A
mbar
B
Flowrate l/h

5.3 Technical data table

Model
3 D 32
Number of elements
no.
3
Max. heating capacity
kW
34.3
Min. heating capacity
kW
16.9
Max. heat output
kW
32
in heating
Min. heat output
kW
16
in heating
Pmax efficiency
%
93.3
(80-60°C)
Efficiency 30%
%
94.3
Efficiency class
Directive 92/42 EEC
Max. working pressure in
bar
6
heating
Min. working pressure in
bar
0.8
heating
Max.
°C
95
heating temperature
Heating
L
12.5
water content
Protection rating
IP
X0D
Power supply voltage
V/Hz
230/50
Electrical power input
W
5
Empty weight
kg
137
Combustion chamber
mm
365
length
Combustion chamber
mm
326
diameter
Pressure loss on fumes
mbar
0.16
side
Type of unit
PIN CE
16
EN
3500
4000
4500
5000
B
3 D 45
3 D 59
3 D 74
3 D 90
4
5
6
7
48.2
62.9
78.8
95.7
34.1
46.8
59.5
72.0
45
59
74
90
32
44
56
68
93.4
93.8
93.9
94
94.1
94
94.3
94.5
6
6
6
6
0.8
0.8
0.8
0.8
95
95
95
95
17
21.5
26
31
X0D
X0D
X0D
X0D
230/50
230/50
230/50
230/50
5
5
5
5
179
221
263
305
465
565
665
765
326
326
326
326
0.3
0.4
0.5
0.6
B
23
0035BT0103
cod. 3540Z230 - 01/2011 (Rev. 00)
5500
(Q)
(Q)
(P)
(P)
(PMS)
(tmax)
AXE 3 D

Publicidad

Tabla de contenido
loading