resideo Braukmann UMV500-LF Series Manual De Instrucciones página 2

Válvula termostática universal under sink
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

UMV500 SERIES
SPECIFICATIONS
Model: UMV500-LF/U Under Sink Mixing Valve.
Construction Materials:
Forged brass body and EPDM seals.
Stainless steel spring.
Working Pressure:
Minimum: 20 psi (138 kPa).
Maximum: 125 psi (861 kPa).
Pressure difference between Hot and Cold inlets shall be
less than 20%.
Connections: 3/8 in. (9.5 mm) compression-type fittings
on end connections.
Valves: Integral check valves in both Hot and Cold ports.
Flow:
Maximum flow: 4.3 Gpm (16.5 l/min) (Cv= 0.36)
Minimum flow: 0.25 Gpm (0.95 l/min)
Cold inlet temperature: 39°F - 80°F (4°C - 27°C)
Hot inlet temperature: 120°F - 180°F (49°C - 82°C)
Valve inlet temperature operating parameters:
The hot inlet temperature must be at least 18°F (10°C)
higher than the mixed outlet temperature.
The cold inlet temperature must be at least 18°F (10°C)
lower than the mixed outlet temperature.
Mixed Outlet Temperature:
80° - 120°F (27° - 49°C).
Approvals:
ASSE 1070 Listed
CSA Certified/Listed
IAPMO/UPC Listed
NSF61/372 Compliant
38-00056EFS—07
INSTALLATION AND
TEMPERATURE ADJUSTMENT
Fig. 2 shows a typical installation for the under sink
mixing valve.
MIXED
WATER
COLD
HOT
WATER
WATER
INLET
INLET
UMV500-LF/U 3-PORT OPTION
TYPICALLY USED IN PUBLIC
FACILITIES AND OFFICE
BUILDINGS WHERE A CONSISTENT
TEMPERATURE IS REQUIRED.
Fig. 2. Typical Installation.
The handwheel of the under sink mixing valve can be
used as a tool to adjust the temperature setting as
follows.
1. The valve must be adjusted when installed. Turn on
the hot and cold supply, then open the hot faucet
served by the valve. Let the water run for several
minutes to ensure maximum hot inlet temperature
is reached.
2. Remove the cap by pulling it off. See Fig. 3.
Fig. 3. Remove the handwheel.
3. Use the cap upside down to adjust the outlet
temperature with a thermometer under the faucet.
Turn the hand wheel clockwise for cooler
temperatures and counterclockwise for warmer
temperatures. See Fig. 4 and 5.
• Turn clockwise to decrease the temperature
down to 80°F;
• Turn counter-clockwise to increase the
temperature up to 120°F.
4. Replace the cap after adjustment to lock the
setting. See Fig. 6.
2
MIXED
COLD
WATER
WATER
HOT
COLD
WATER
WATER
INLET
INLET
UMV500-LF/U 4-PORT OPTION
TYPICALLY USED IN HOMES,
APARTMENTS, HOTELS AND
LOCATIONS WHERE THE USER
IS FREE TO ADJUST THE WATER
TEMPERATURE.
M36831
M36799

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Braukmann umv500-u series

Tabla de contenido